Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 4: Multi F MAX with LGRED Electrical Data.
GENERAL DATA
Multi F MAX with LGRED Outdoor Unit Electrical Data
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
follows: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Indoor Fan Motor (FLA) is based on the max. combination
of IDUs.
Nominal
Tons
Unit Model
No.
Phase Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Outdoor Unit Fan
Motor(s)
Indoor
Unit Fan
Motor
kW x Qty. FLA x Qty. FLA
3.0 LMU361HHV
1 60 208 -230 187 - 253
32.7 40 1 22.0 0.12 x 2 1.60 x 2 3.6
3.5 LMU421HHV 32.7 40 1 22.0 0.12 x 2 1.60 x 2 4.2
4.0 LMU480HHV 32.7 40 1 22.0 0.12 x 2 1.60 x 2 4.9