Multi F Installation Manual

62
MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Forced Cooling Operation Function
Use to add refrigerant to the system when outside ambient temperatures are cool (ex.: winter).
1. Shut power down to the system.
2. Set DIP Switch 1 to ON.
3. Turn power on to the system.
4. Verify that the Red LED on the outdoor unit PCB is ON (indicates indoor units are in forced cooling
operation).
5. Add refrigerant.
,IWKHJUHHQ/('OLJKWRQWKHRXWGRRUXQLW3&%LV21LWLQGLFDWHVWKHFRPSUHVVRULV2))GXHWRORZSUHVVXUHLQWKHV\VWHP
Turn DIP Switch 1 to OFF after finishing (Normal Operation setting).
2QO\WKHILUVWIRXU',3VZLWFKHVDUHIXQFWLRQDORQWKH/08+9
Multi F LMU18CHV and LMU24CHV
DI P- SW
SW01 N
DIP SW 2
Multi F LMU30CHV and LMU36CHV
Multi F MAX LMU480HV and LMU540HV
DIP-SW01D
12345678910
Multi F MAX LMU600HV
Location of DIP Switches on Multi F and Multi F MAX Outdoor Units
DIP SWITCH SETTINGS
Figure 89: Multi F / Multi F MAX Outdoor Unit DIP Switch Locations.
12 43
12 43
ON
OFF
Figure 90: Forced Cooling DIP
Switch Setting.