SINGLE ZONE WALL MOUNTED ART COOL™ PREMIER ENGINEERING MANUAL 3/4, 1, 1-1/4, 1-1/2, and 2 Tons Models: LA090HYV3 LA120HYV3 LA150HYV3 LA180HYV3 LA240HYV3
PROPRIETARY DATA NOTICE This document, as well as all reports, illustrations, data, information, and other materials are the property of LG Electronics U.S.A., Inc., and are disclosed by LG Electronics U.S.A., Inc. only in confidence. This document is for design purposes only. A summary list of safety precautions is on page 4. For more technical materials such as submittals, catalogs, installation, owner’s, and service manuals, visit www.lghvac.com. For continual product development, LG Electronics U.S.
About LG Electronics, Inc. LG Electronics, Inc. is a global leader and technology innovator in consumer electronics, mobile communications, and home appliances. LG Electronics, Inc. comprises five business units— Home Entertainment, Mobile Communications, Air Conditioning, Business Solutions, and Home Appliance. LG is one of the world’s leading producers of flat panel televisions, audio and video products, mobile handsets, air conditioners, and washing machines.
TABLE OF CONTENTS INTRODUCTION...................................................................................... 5 Architectural Appeal.............................................................................. 6 Convergence of Technological Innovation with Flexibility and Style ���� 6 Product Features and Benefits............................................................. 8 Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Unit Nomenclature............................................
INTRODUCTION “Architectural Appeal” on page 6
ARCHITECTURAL APPEAL Convergence of Technological Innovation with Flexibility and Style Benefits of Single Zone Wall Mounted Art Cool Premier System Single Zone Wall Mounted Art Cool™ Premier Engineering Manual • Available in 9,000, 12,000, 15,000, 18,000, and 24,000 Btu/h • Inverter technology • All-season use - heat pump models for both cooling and heating capabilities • Operating range for outdoor units of 14°F to 118°F (DB) in cooling and -13°F to 65°F (WB) in heating • Operating range for indoor uni
PRODUCT DATA “Product Features and Benefits” on page 8 “Unit Nomenclature” on page 9 “General Data” on page 10 “Electrical Data” on page 13 “Functions, Controls, Options” on page 14 “Outdoor Unit Dimensions” on page 15 “Outdoor Unit Center of Gravity / Corner Weight” on page 17 “Indoor Unit Dimensions” on page 18 “Acoustic Data” on page 20 “Refrigerant Flow Diagrams” on page 24 “Indoor Unit Wiring Diagram” on page 26 “Outdoor Unit Wiring Diagram” on page 27 “Accessories” on page 29
PRODUCT FEATURES AND BENEFITS Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Single Zone Wall Mounted Art Cool Premier Single zone systems are equipped with inverter components that offer superior load matching and long piping installation. The product works for optimizing power consumption in residential and small office buildings. Utilizing multiple indoor wall mount units each with custom temperature controls allow for precise temperature settings in each zone of the building.
UNIT NOMENCLATURE Single Zone Wall Mount Indoor and Outdoor Units LA N 150 HYV 3 Family LA= Art Cool Premier Type N = Indoor Wall Mount Unit U = Outdoor Heat Pump Unit Product Data Nominal Capacity (Nominal cooling capacity in Btu/h) 090 = 9,000 120 = 12,000 150 = 15,000 180 = 18,000 240 = 24,000 Indoor/Outdoor Product HYV = Art Cool Premier Generation or Revision 3 = Third Due to our policy of continuous product innovation, some specifications may change without notification.
GENERAL DATA Art Cool Premier Pairing Table The following table shows the available outdoor and indoor units, along with the factory provided controller.
GENERAL DATA Table 2: Single Zone Wall Mounted Art Cool Premier System Specifications. System Model Number (IDU/ODU) LA120HYV3 (LAN120HYV3/LAU120HYV3) 1,023 ~ 9,000 ~ 13,000 0.20 ~ 0.57 ~ 0.74 1,023 ~ 11,000 ~ 20,472 0.195 ~ 0.71 ~ 0.93 4.54 1,023 ~ 12,000 ~ 13,785 0.20 ~ 0.87 ~ 1.14 1,023 ~ 13,600 ~ 22,178 0.195 ~ 0.97 ~ 1.25 4.11 11,940 (108%) 11,000 (100%) 8,030 (73%) 15.79 27.5 13.5 14,760 (109%) 13,600 (100%) 9,640 (70%) 13.79 25.5 12.
GENERAL DATA Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Table 3: Single Zone Wall Mounted Art Cool Premier System Specifications, continued.
ELECTRICAL DATA Table 4: Single Zone Wall Mounted Art Cool Premier System Electrical Data Table. Model Number Nominal Tons Compressor Qty. Compressor (A) Cool/Heat Fan Qty. ODU Fan (A) IDU Fan (A) MCA(A) MOP(A) LA090HYV3 3/4 1 8.3/8.3 1 0.4 0.4 11.2 15 LA120HYV3 1 1 8.3/8.3 1 0.4 0.4 11.2 15 LA150HYV3 1-1/4 1 14.41/14.41 1 0.4 0.5 19.0 30 LA180HYV3 1-1/2 1 14.41/14.41 1 0.4 0.5 19.0 30 LA240HYV3 2 1 14.41/14.41 1 0.4 0.5 19.
FUNCTIONS, CONTROLS, OPTIONS Table 5: Indoor Units—Functions, Controls and Options.
12-11/16 (322) 5-5/8 (143) 1 34-1/4 (870) 23-1/16 (586) 20-9/32 (515) 2 3-1/16 (78) 7/8 (22) 1-1/32 (26) 12-5/16 (313) 14-13/32 (366) 25-19/32 (650) Drain Hole 6-Ø13/16 (20) 4 6 5 1-1/4 (32) 6-17/32 (166) 7-9/16 (192) 13 (330) 3 3/4 (19) 6-25/32 (172) Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
PRODUCT DATA Unit : inch (mm) 1-1/32 (26) 1 13-7/32 (336) 6-17/32 (166) 7 37-13/12 (950) 24-13/32 (620) Ø22-1/8 (562) Drain Hole 5-Ø13/16 (20) 14-3/16 (360) 2 3 5 6 3-5/32 (80) 2-17/32 (64) 1-9/16 (40) 15-11/32 (390) 32-3/4 (832) | 15/16 (24) 16 15-7/16 (392) ° 25° 14 Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
OUTDOOR UNIT CENTER OF GRAVITY / CORNER WEIGHT Figure 1: Center of Gravity and Corner Weight Dimensions Diagram. d D A e c C B Product Data b a Table 6: Center of Gravity and Corner Weight Dimensions. Model Weight (lb.) Shipping Net Center of Gravity (inch) a b c Leg (inch) d e A Corner Weight (lb.) B C D LAU090HYV3, LAU120HYV3 103.2 93.9 22-1/4 10-1/4 5-29/32 23-1/16 14-13/32 11.1 15.1 35.9 31.8 LAU150HYV3, LAU180HYV3, LAU240HYV3 147.7 135.
1/8(3) x 1/4(6) 1/4(6) x 1/8(3) 1-1/4 (31) 2-7/16 (61.5) 1-3/32 (50.2) 1-1/16 (26.2) 2-3/8 (60) 2-13/32(61) 2-3/8 (60) 1 Unit : inch (mm) 5-31/32 (152) 1-7/16(33.5) 6 [34-11/32 (872)] Air Outlet Hole 39-9/32 (998) [36-5/32 (918)] Air Intake Hole Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp. PRODUCT DATA 2-3/8 (60) 1 1/8(3) x 1/4(6) 1/4(6) x 1/8(3) 1-1/4 (31) 2-7/16 (61.5) 1-3/32 (50.2) 1-1/16 (26.2) 15/32 (12) 2-5/8 (67) 7/16 (11) 5-31/32 (152) 2-13/32(61) 1-9/32(32.7) 1-7/16(33.
OUTDOOR UNIT ACOUSTIC DATA Figure 2: Outdoor Unit Sound Levels 3.28 ft LAU090HYV3 LAU120HYV3 LAU150HYV3 LAU180HYV3 LAU240HYV3 48 48 51 53 55 50 50 56 56 56 Figure 3: Sound Pressure Levels for LAU090HYV3 Outdoor Unit.
OUTDOOR UNIT ACOUSTIC DATA Figure 5: Sound Pressure Levels for LAU150HYV3 Outdoor Unit.
INDOOR ACOUSTIC DATA 3.28 ft 2.62 ft Microphone • • • • Measurements are taken 3.28 ft away from the front of the unit. Sound pressure levels are measured in dB(A) with a tolerance of ±3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Sound level will vary depending on a range of factors including the construction (acoustic absorption coefficient) of a particular room in which the unit was installed.
INDOOR ACOUSTIC DATA Figure 11: Sound Pressure Levels for LAN150HYV3 Indoor Units.
REFRIGERANT FLOW DIAGRAMS Single Zone Wall Mounted Art Cool™ Premier Engineering Manual LAU/LAN090HYV3, LAU/LAN120HYV3 Thermistor Description PCB Connector TH1 Indoor air temperature thermistor CN-TH1 (Indoor) TH2 Evaporator middle temperature thermistor CN-TH3 (Indoor) TH3 Water level sensor (optional) CN-TH2 (Indoor) TH4 Outdoor air temperature thermistor TH5 Condensing temperature thermistor TH6 Discharge pipe temperature thermistor CN-TH1 (Outdoor) CN-TH2 (Outdoor) M Heat Exchange
REFRIGERANT FLOW DIAGRAMS LAU/LAN150HYV3, LAU/LAN180HYV3, LAU/LAN240HYV3 Indoor Unit Outdoor Unit Field Pipin g (ϕ3/8” Copper Tubing) 3-W ay Valve Liquid Side EEV M Th1 Heat Exchanger (Evaporator) Th4 Heat Exchanger (Condenser) M Th2 3-W ay Valve Th3 Reversing Valve Field Pipin g (ϕ5/8” Copper Tubing) Th5 Gas Side Product Data Th6 Accumulator : Cooling : Heating Compressor Thermistor Description PCB Connector TH1 Indoor air temperature thermistor CN-TH1 (Indoor) TH2 Evaporator mid
WIRING DIAGRAM LAN090HYV3, LAN120HYV3, LAN150HYV3, LAN180HYV3, LAN240HYV3 Factory Wiring Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Field Wiring Option 26 | PRODUCT DATA Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
WIRING DIAGRAM LAU090HYV3, LAU120HYV3 Factory Wiring Field Wiring Option Product Data Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
WIRING DIAGRAM LAU150HYV3, LAU180HYV3, LAU240HYV3 Factory Wiring Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Field Wiring Option 28 | PRODUCT DATA Due to our policy of continuous product innovation, some specifications may change without notification. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
ACCESSORIES LG Monitoring View (LGMV) Diagnostic Software and Cable LGMV software allows the service technician or commissioning agent to connect a computer USB port to the outdoor unit main printed circuit board (PCB) using an accessory cable without the need for a separate interface device.
PERFORMANCE DATA “Cooling Capacity” on page 31 “Maximum Cooling Capacity” on page 34 “Heating Capacity” on page 37 “Maximum Heating Capacity” on page 40 “Air Flow and Temperature Distributions Graphs” on page 43
PERFORMANCE DATA Cooling Capacity LA090HYV3, LA120HYV3 Table 9: LAN090HYV3/LAU090HYV3 Cooling Capacities. Outdoor Air 64 / 53 Temp. (°F DB) TC SHC 5.45 5.34 5.38 5.44 5.51 5.92 6.01 6.24 6.47 6.70 6.94 7.17 7.40 7.63 7.56 7.49 7.43 7.36 7.29 7.22 7.15 6.96 6.77 6.59 6.35 6.21 4.61 4.55 4.59 4.65 4.74 5.09 5.17 5.36 5.56 5.76 5.96 6.16 6.36 6.56 6.50 6.44 6.38 6.32 6.27 6.21 6.15 5.99 5.82 5.66 5.46 5.34 PI 0.22 0.23 0.23 0.24 0.24 0.24 0.25 0.26 0.28 0.30 0.32 0.34 0.35 0.37 0.39 0.41 0.43 0.45 0.47 0.
PERFORMANCE DATA Cooling Capacity LA150HYV3, LA180HYV3 Table 11: LAN150HYV3/LAU150HYV3 Cooling Capacities. Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Outdoor Air 64 / 53 Temp. TC SHC (°F DB) 0 5 7 10 14 23 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 118 9.08 8.91 8.97 9.06 9.18 9.86 10.01 10.40 10.79 11.17 11.56 11.95 12.34 12.72 12.61 12.49 12.38 12.26 12.14 12.03 11.91 11.60 11.29 10.98 10.59 10.35 7.45 7.35 7.41 7.52 7.65 8.22 8.35 8.67 8.99 9.31 9.64 9.96 10.
PERFORMANCE DATA Cooling Capacity LA240HYV3 Table 13: LAN240HYV3/LAU240HYV3 Cooling Capacities. Outdoor Air 64 / 53 Temp. (°F DB) TC SHC 13.32 13.07 13.16 13.29 13.47 14.46 14.69 15.25 15.82 16.39 16.96 17.52 18.09 18.66 18.49 18.32 18.15 17.98 17.81 17.64 17.47 17.01 16.56 16.10 15.53 15.18 10.35 10.20 10.29 10.44 10.62 11.41 11.59 12.03 12.48 12.93 13.38 13.82 14.27 14.72 14.59 14.45 14.32 14.19 14.05 13.92 13.79 13.43 13.06 12.70 12.25 11.98 PI 0.66 0.69 0.70 0.71 0.72 0.71 0.73 0.79 0.84 0.89 0.
PERFORMANCE DATA Maximum Cooling Capacity LA090HYV3, LA120HYV3 Table 14: LAN090HYV3/LAU090HYV3 Maximum Cooling Capacities. Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Outdoor Air 64 / 53 Temp. TC SHC (°F DB) 0 5 7 10 14 23 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 118 3.96 4.00 4.05 4.13 4.23 3.51 3.51 3.50 3.48 3.47 3.46 3.45 3.44 3.43 3.31 3.20 3.09 2.97 2.86 2.75 2.63 2.25 1.87 1.49 1.16 0.96 3.56 3.71 3.75 3.81 3.90 3.25 3.25 3.23 3.22 3.21 3.19 3.18 3.17 3.15 3.
PERFORMANCE DATA Maximum Cooling Capacity LA150HYV3, LA180HYV3 Table 16: LAN150HYV3/LAU150HYV3 Maximum Cooling Capacities. Outdoor Air 64 / 53 Temp. TC SHC (°F DB) 12.13 12.19 12.29 12.43 12.62 11.30 11.29 11.27 11.25 11.23 11.21 11.19 11.17 11.15 10.94 10.73 10.52 10.31 10.10 9.90 9.69 8.99 8.29 7.59 6.98 6.62 11.52 11.78 11.85 11.96 12.11 10.96 10.95 10.93 10.90 10.88 10.86 10.83 10.81 10.78 10.61 10.44 10.26 10.09 9.92 9.75 9.57 8.93 8.29 7.59 6.98 6.62 0.24 0.27 0.27 0.28 0.29 0.36 0.36 0.37 0.38 0.
PERFORMANCE DATA Maximum Cooling Capacity LA240HYV3 Table 18: LAN240HYV3/LAU240HYV3 Maximum Cooling Capacities. Outdoor Air 64 / 53 Temp. TC SHC (°F DB) Single Zone Wall Mounted Art Cool™ Premier Engineering Manual 0 5 7 10 14 23 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 118 13.43 13.49 13.59 13.73 13.92 12.60 12.59 12.57 12.55 12.53 12.51 12.49 12.46 12.44 12.24 12.03 11.82 11.61 11.40 11.19 10.99 10.29 9.59 8.89 8.28 7.91 11.52 11.78 11.85 11.96 12.11 10.96 10.95 10.93 10.90 10.
PERFORMANCE DATA Heating Capacity LA090HYV3, LA120HYV3 Table 19: LAN090HYV3/LAU090HYV3 Heating Capacities. Outdoor Air Temp. °F DB °F WB -13 -4 -1 0 5 9 14 15 17 23 30 38 40 43 50 53 57 61 65 TC 60 5.08 5.61 6.11 6.19 6.46 6.75 6.96 7.01 7.10 7.79 9.34 10.71 11.06 11.57 11.69 11.96 12.21 12.44 12.62 PI 0.43 0.47 0.52 0.53 0.54 0.56 0.57 0.57 0.58 0.61 0.65 0.70 0.71 0.72 0.73 0.74 0.75 0.76 0.77 TC 64 4.93 5.44 5.92 6.00 6.27 6.54 6.75 6.80 6.89 7.55 9.06 10.39 10.72 11.22 11.34 11.59 11.84 12.
PERFORMANCE DATA Heating Capacity LA150HYV3, LA180HYV3 Table 21: LAN150HYV3/LAU150HYV3 Heating Capacities. Outdoor Air Temp. Single Zone Wall Mounted Art Cool™ Premier Engineering Manual °F DB °F WB -12 -3 0 1 6 10 16 17 19 24 32 41 43 47 53 59 64 70 75 -13 -4 -1 0 5 9 14 15 17 23 30 38 40 43 50 53 57 61 65 Indoor Air Temperature (°F DB/ °F WB) TC 60 8.31 9.18 10.00 10.12 10.58 11.04 11.39 11.47 11.62 12.75 15.28 17.53 18.10 18.94 19.13 19.57 19.98 20.36 20.65 PI 0.69 0.75 0.82 0.83 0.86 0.89 0.
PERFORMANCE DATA Heating Capacity LA240HYV3 Table 23: LAN240HYV3/LAU240HYV3 Heating Capacities. Outdoor Air Temp. °F DB °F WB -13 -4 -1 0 5 9 14 15 17 23 30 38 40 43 50 53 57 61 65 TC 12.01 13.26 14.44 14.62 15.28 15.95 16.45 16.56 16.79 18.41 22.07 25.33 26.14 27.36 27.63 28.26 28.86 29.41 29.82 PI 1.27 1.39 1.52 1.54 1.59 1.64 1.66 1.68 1.71 1.77 1.92 2.04 2.07 2.12 2.14 2.16 2.21 2.24 2.27 TC 11.65 12.86 14.00 14.18 14.81 15.47 15.95 16.06 16.28 17.86 21.40 24.56 25.35 26.53 26.79 27.40 27.99 28.
PERFORMANCE DATA Maximum Heating Capacity LA090HYV3, LA120HYV3 Table 24: LAN090HYV3/LAU090HYV3 Maximum Heating Capacities. Outdoor Air Temp. Single Zone Wall Mounted Art Cool™ Premier Engineering Manual °F DB °F WB -12 -3 0 1 6 10 16 17 19 24 32 41 43 47 53 59 64 70 75 -13 -4 -1 0 5 9 14 15 17 23 30 38 40 43 50 53 57 61 65 Indoor Air Temperature (°F DB/ °F WB) TC 60 7.94 9.81 10.35 10.59 11.42 11.93 12.09 12.19 12.25 13.81 16.48 19.01 19.81 20.88 21.35 21.86 22.08 22.13 22.20 PI 0.91 0.95 0.96 0.
PERFORMANCE DATA Maximum Heating Capacity LA150HYV3, LA180HYV3 Table 26: LAN150HYV3/LAU150HYV3 Maximum Heating Capacities. Outdoor Air Temp. °F DB °F WB -13 -4 -1 0 5 9 14 15 17 23 30 38 40 43 50 53 57 61 65 TC 60 14.54 17.06 17.84 18.17 19.33 20.25 21.33 21.49 21.94 23.05 24.19 25.26 25.49 25.80 26.39 26.68 26.87 26.95 26.89 PI 1.94 2.03 2.05 2.07 2.12 2.13 2.15 2.16 2.17 2.18 2.12 2.00 1.92 1.86 1.89 1.86 1.82 1.75 1.62 TC 64 14.59 16.98 17.74 18.05 19.18 20.08 21.13 21.29 21.73 22.84 23.96 25.
PERFORMANCE DATA Maximum Heating Capacity LA240HYV3 Table 28: LAN240HYV3/LAU240HYV3 Maximum Heating Capacities. Outdoor Air Temp. °F DB °F WB Single Zone Wall Mounted Art Cool™ Premier Engineering Manual -12 -3 0 1 6 10 16 17 19 24 32 41 43 47 53 59 64 70 75 -13 -4 -1 0 5 9 14 15 17 23 30 38 40 43 50 53 57 61 65 Indoor Air Temperature (°F DB/ °F WB) TC 60 17.02 21.44 22.66 23.16 25.71 27.05 28.30 28.62 28.97 30.44 32.78 35.41 36.00 37.19 38.16 38.64 38.95 39.08 38.98 PI 2.74 2.87 2.90 2.90 3.00 3.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN090HYV3 Cooling Air Velocity [m/s (ft./s)] 0.5(1.6) 0.3(1) Temperature [°C (°F)] 2(6.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 29(84) 28(82) 26(79) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 Side View ) Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] m ft. 5 16.4 m ft. 5 16.4 0.5(1.6) 4 13.1 0.3(1) 3 9.8 0.3(1) 0.5(1.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN090HYV3, continued. Heating Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Air Velocity [m/s (ft./s)] Temperature [°C (°F)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 m 24(75) 23(73) 25(77) 26(79) 2 ft. 6.6 1 3.3 0 0 m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN120HYV3 Cooling Air Velocity [m/s (ft./s)] 0.5(1.6) 0.3(1) Temperature [°C (°F)] 2(6.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 29(84) 28(82) 26(79) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 Side View ) Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] m ft. 5 16.4 m ft. 5 16.4 0.5(1.6) 4 13.1 0.3(1) 3 9.8 0.3(1) 0.5(1.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN120HYV3, continued. Heating Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Air Velocity [m/s (ft./s)] Temperature [°C (°F)] 2(6.6) 0.3(1) 0.5(1.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 m 24(75) 23(73) 25(77) 26(79) 2 ft. 6.6 1 3.3 0 0 m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN150HYV3 Cooling Air Velocity [m/s (ft./s)] 0.5(1.6) Temperature [°C (°F)] 2(6.6) 1(3.3) 0.3(1) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 26(79) 28(82) 22(72) 18(64) 2 m ft. 6.6 1 3.3 0 0 m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 Side View ) Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] m ft. 5 16.4 0.3(1) 4 13.1 m ft. 5 16.4 1(3.3) 1(3.3) 2(6.6) 2 6.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN150HYV3, continued. Heating Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Air Velocity [m/s (ft./s)] Temperature [°C (°F)] 0.5(1.6) 0.3(1) 2(6.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 24(75) 30(86) 32(90) 26(79) 22(72) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN180HYV3 Cooling Air Velocity [m/s (ft./s)] 0.5(1.6) Temperature [°C (°F)] 2(6.6) 1(3.3) 0.3(1) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 26(79) 28(82) 22(72) 18(64) 2 m ft. 6.6 1 3.3 0 0 m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 Side View ) Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] m ft. 5 16.4 0.3(1) 4 13.1 m ft. 5 16.4 1(3.3) 1(3.3) 2(6.6) 2 6.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN180HYV3, continued. Heating Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Air Velocity [m/s (ft./s)] Temperature [°C (°F)] 0.5(1.6) 0.3(1) 2(6.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 24(75) 30(86) 32(90) 26(79) 22(72) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN240HYV3 Cooling Air Velocity [m/s (ft./s)] 0.5(1.6) Temperature [°C (°F)] 2(6.6) 1(3.3) 0.3(1) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 26(79) 28(82) 22(72) 18(64) 2 m ft. 6.6 1 3.3 0 0 m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 Side View ) Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] m ft. 5 16.4 0.3(1) 4 13.1 m ft. 5 16.4 1(3.3) 1(3.3) 2(6.6) 2 6.
PERFORMANCE DATA Air Flow and Temperature Distribution Graphs LAN240HYV3, continued. Heating Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Air Velocity [m/s (ft./s)] Temperature [°C (°F)] 0.5(1.6) 0.3(1) 2(6.6) 1(3.3) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.3 0 0 24(75) 30(86) 32(90) 26(79) 22(72) m 10 8 6 4 2 0 ft. 32.8 26.2 19.7 13.1 6.6 0 m 2 ft. 6.6 1 3.
APPLICATION GUIDELINES “Equipment Selection Procedure” on page 54 “Building Ventilation Design Guide” on page 56 55 “Placement Considerations” on page 57
EQUIPMENT SELECTION PROCEDURE Cooling/Heating Correction Factors Single Zone Wall Mounted Art Cool™ Premier Engineering Manual For Single Zone Art Cool Premier systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction factors as shown in the table below.
BUILDING VENTILATION DESIGN GUIDE Building Ventilation Design Guide ASHRAE 62.1 and local codes specify the minimum volume of outdoor air that must be provided to an occupied space. Outdoor air is required to minimize adverse health effects, and it provides acceptable indoor air quality for building occupants. The three methods of accomplishing this with single zone systems are summarized here.
BUILDING VENTILATION DESIGN GUIDE Method 2: Unconditioned Outdoor Air (Non-Ducted, Natural Ventilation) Natural ventilation devices, such as operable windows or louvers may be used to ventilate the building when local code permits. The open area of a window or the free area of a louver must meet the minimum percentage of the net occupied floor area. Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Advantages • Occupants control the volume of the ventilation air manually.
PLACEMENT CONSIDERATIONS Selecting the Best Location DANGER To avoid the possibility of fire, do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak. Failure to do so will cause serious bodily injury or death. Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from accessing it. where acidic solution and spray (sulfur) are often used as this may cause serious bodily injury or death.
PLACEMENT CONSIDERATIONS Indoor Unit Clearance/Outdoor Unit Installation Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Indoor Unit Best Location Figure 17: Single Zone Indoor Unit Clearance Requirements. Follow recommended best practices when choosing an indoor location for the single zone indoor unit. • Use a metal detector to locate studs in the walls. Anchor unit following stud location, to prevent damage to the wall.
PLACEMENT CONSIDERATIONS Outdoor Unit Clearances Minimum Clearance Requirements for Single Zone Art Cool Premier Systems Proper clearance for the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet and outlet and minimum allowable space requirements as illustrated in the diagrams below. Specific clearance requirements in the diagram below are for the Single Zone Wall Mounted Art Cool Premier systems.
REFRIGERANT PIPING DESIGN & LAYOUT BEST PRACTICES “Refrigerant Piping Design” on page 61 "Selecting Field-Supplied Copper Tubing" on page 62 "Refrigerant Piping System Layout" on page 63 "Electrical Connections" on page 67
REFRIGERANT PIPING DESIGN Design Guideline Summary/Selecting Field-Supplied Copper Tubing Device Connection Limitations Single-zone systems consist of one outdoor unit and one indoor unit. One of the most critical elements of a single zone system is the refrigerant piping. The table below lists pipe length limits that must be followed in the design of a Single Zone Wall Mounted Art Cool Premier refrigerant pipe system. Refer to the figure for maximum length and elevation of piping.
REFRIGERANT PIPING DESIGN Selecting Field-Supplied Copper Tubing Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Table 33: Linear Thermal Expansion of Copper Tubing in Inches. Pipe Length1 10 20 30 40 50 60 1 35° 0.04 0.08 0.12 0.16 0.20 0.24 40° 0.04 0.08 0.12 0.16 0.20 0.24 45° 0.05 0.10 0.15 0.20 0.25 0.30 50° 0.06 0.12 0.18 0.24 0.30 0.36 55° 0.06 0.13 0.20 0.26 0.33 0.39 60° 65° 0.07 0.14 0.21 0.28 0.35 0.42 70° 0.08 0.15 0.23 0.30 0.38 0.45 0.08 0.16 0.24 0.32 0.40 0.
INSTALLATION & LAYOUT BEST PRACTICES Refrigerant Piping System Layout Field-Provided Isolation Ball Valves Obstacles 3X When an obstacle, such as an I-beam or concrete T, is in the path of the planned refrigerant pipe run, it is best practice to route the pipe over the obstacle. If adequate space is not available to route the insulated pipe over the obstacle, then route the pipe under the obstacle.
INSTALLATION & LAYOUT BEST PRACTICES Refrigerant Piping System Layout Pipe Sleeves at Penetrations LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve. Underground refrigerant pipe shall be routed inside a protective sleeve to prevent insulation deterioration See figure below.
INSTALLATION & LAYOUT BEST PRACTICES Refrigerant Piping System Layout Single Zone Art Cool Premier Outdoor Unit Connections 1. Remove the tubing cover from the unit by loosening the fastening screws. 2. Align the center of the refrigerant pipe and corresponding connection. 3. Place a couple of drops of refrigerant oil on the opening rim of the flare before assembling. add any contaminants. Tighten the flare nut initially by hand. 4.
INSTALLATION & LAYOUT BEST PRACTICES Refrigerant Piping System Layout Refrigerant Piping / Brazing Practices Single Zone Wall Mounted Art Cool™ Premier Engineering Manual It is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust during installation. All joints are brazed in the field. Single Zone Wall Mounted Art Cool Premier Figure 33: Refrigerant Pipe Brazing.
ELECTRICAL CONNECTIONS Outdoor Electrical Connection Figure 35: LAU150HYV3/ LAU180HYV3/LAU240HYV3 Outdoor Unit Electrical Connection. Terminal Block 1(L1) 2(L2) 3 1(L1) 2(L2) Over 0.2” Terminal Block Connecting Cable Over 0.2” Power Supply Cord Power Supply Cord Conduit Panel Conduit Panel Tubing Cover Connecting Cable Terminal Cover Figure 36: Circuit Breaker. • Separately wire the high and low voltage lines. There is a risk of electric shock, physical injury, or death.
TECHNICAL DATA “Mechanical Specifications” on page 69 “Acronyms” on page 70
MECHANICAL SPECIFICATIONS Single Zone Wall Mounted Art Cool Premier General Temperature Ranges Outdoor Unit Operating ranges for Outdoor units of 14°F to 118°F DB for cooling; -13°F to 65°F WB for heating. Indoor Unit Operating ranges for Indoor Units of 53°F to 75°F WB for cooling; 60°F to 86°F DB for heating. (Installing an optional Low Ambient Wind Baffle Kit will allow operation down to 0°F in cooling mode for these single zone systems.
ACRONYMS Single Zone Wall Mounted Art Cool™ Premier Engineering Manual Table 40: Table of Acronyms.
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. Commercial Air Conditioning Division 4300 North Point Parkway Alpharetta, Georgia 30022 www.lg-dfs.