EQUIPMENT SELECTION PROCEDURE
Cooling/Heating Correction Factors
For Single Zone Art Cool Premier systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, de-
termine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction
factors as shown in the table below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity tables using
design conditions. The resultant is the NET cooling or heating capacity.
Table 29: Single Zone Wall Mounted Art Cool Premier Cooling/Heating % Coefcient Factors.
Model Main Piping Length
Indoor Unit Outdoor Unit Feet 16.4 24.6 32.8 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0
LAN090HYV3 LAU090HYV3
Cooling 100 100 99.0 97.0 95.0 - - - - - -
Heating 100 100 99.2 97.6 96.0 - - - - - -
LAN120HYV3 LAU120HYV3
Cooling 100 100 99.0 97.0 95.0 - - - - - -
Heating 100 100 99.2 97.6 96.0 - - - - - -
LAN150HYV3 LAU150HYV3
Cooling 100 100 99.6 98.7 97.8 96.9 96.0 95.1 94.3 93.4 92.5
Heating 100 100 99.8 99.3 98.9 98.4 98.0 97.5 97.1 96.6 96.2
LAN180HYV3 LAU180HYV3
Cooling 100 100 99.6 98.7 97.8 96.9 96.0 95.1 94.3 93.4 92.5
Heating 100 100 99.8 99.3 98.9 98.4 98.0 97.5 97.1 96.6 96.2
LAN240HYV3 LAU240HVY3
Cooling 100 100 99.6 98.7 97.8 96.9 96.0 95.1 94.3 93.4 92.5
Heating 100 100 99.8 99.3 98.9 98.4 98.0 97.5 97.1 96.6 96.2