Specification Guide

MultiSITE™ CRC1 - PREMTBVC0
MultiSITE CRC1+ - PREMTBVC1
Dry Contact - PDRYCB300
Job Name/Locaon:
Date:
PO No.:
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)
For: File Resubmit
Approval Other
Tag #:
For a complete list of available accessories, contact your LG representave.
For connual product development, LG reserves the right to change specicaons without noce.
© LG Electronics U.S.A., Inc., Englewood Clis, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
1. Acceptable operang voltage: 187V-253V.
2. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
3. See Engineering Manual for sensible and latent capacies.
4. All communication / connection (power) cable from the outdoor unit to the indoor unit is field supplied
and must be a minimum of four-conductor, 18 AWG, stranded, shielded or unshielded (if shielded, it must be
grounded to the chassis of the outdoor unit only), and must comply with applicable local and national codes.
5. Power wiring cable size must comply with the applicable local and naonal code.
6. The indoor unit comes with a dry helium charge.
7. Corresponding refrigerant piping length is in accordance with standard length of each outdoor unit and the
level dierence is 0 . All capacies are net with a combinaon rao between 95 - 105%.
8. Must follow installaon instrucons in the applicable LG installaon manual.
Notes:
Controls Features:
• 4-Way auto swing
• 24-Hour on/o mer
• Auto operaon
• Auto restart
• Chaos wind
• Inverter (variable speed fan)
• Jet cool/Jet heat
• 3M Micro Filter
• Self-cleaning indoor coil
• Sleep mode
• Condensate sensor connecon
• Built-in Wi-Fi via Smart ThinQ app
• Compable with Single Zone
HSV5 Outdoor Units
Oponal Accessories:
Cooling (°F DB)
Heang (°F WB)
57 ~ 77
59 ~ 81
Entering Mixed Air:
Page 1 of 2
Included Accessories:
• Wireless Remote Controller — AKB74955602
Performance:
Nominal Cooling Capacity (Btu/h)
Nominal Heang Capacity (Btu/h)
Cooling Nominal Test Condions:
Indoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB
Heang Nominal Test Condions:
Indoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB
Electrical:
Power Supply (V¹/Hz/Ø)
Rated Amps (A)
208-230/60/1
0.4
Piping:
Installed Liquid Pipe (in., O.D.)
Installed Vapor Pipe (in., O.D.)
Liquid Connecon (in., O.D.)
Vapor Connecon (in., O.D.)
Drain (in., O.D. / I.D.)
Temperature Sensor
27/32 , 5/8
Thermistor
Unit Data:
Refrigerant Type
Refrigerant Control
Sound Pressure (H/M/L) (±3 dB[A])
2
Primary Filter
Secondard Filter
Net Weight (lbs.)
Shipping Weight (lbs.)
R410A
EEV
Washable Pre-lter
3M Micro Dust
Fan:
Type
Quanty
Motor/Drive
Air Flow H/M/L (CFM)
Cross Flow
1
Brushless Digitally Controlled/Direct
18,000
Multi F Wall Mounted Art Cool™ Mirror Indoor Unit
ø1/2
ø3/8
ø5/8
29.8
21,600
44 / 38 / 34
ø1/4
SB_MultiF_ArtCool_Mirror_IDU_LAN180HSV5_2018_03_20_062643
9. Multi compatible 18k IDUs include socket adapters for refrigerant pipe connections with Multi F systems.
558 / 438 / 353
LAN180HSV5
18,000 Btu/h
36.4

Summary of content (2 pages)