Single Zone High Efciency Wall Mounted Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Model Number Nom. Tons
Compressor
Qty
Compressor
(A) Cool/Heat
Fan Qty ODU Fan (A) IDU Fan (A) MCA (A) MOP (A)
LS090HSV4 3/4 1 8.3/8.3 1 0.40 0.40 10 15
LS120HSV4 1 1 8.3/8.3 1 0.40 0.40 10 15
LS180HSV4 1-1/2 1 14.6/14.6 1 0.25 0.40 19 25
Table 2: Single Zone High Efciency Indoor Unit Electrical Data
Electrical/R410A Refrigerant
• Piping wall thickness must comply with the applicable local, state, and federal codes for the 551 psi design pressure of R410A.
• Because R410A is a combination of R32 and R125, the required additional refrigerant must be charged in its liquid state. If the refrig-
erant is charged in its gaseous state, its composition changes and the system will not work properly.
R410A Refrigerant
R410A refrigerant has a higher operating pressure in comparison to R22 refrigerant and, therefore, all piping system materials installed must
have a higher resisting pressure than the materials traditionally used in R22 systems.
R410A refrigerant is an azeotrope of R32 and R125, mixed at 50:50, so the ozone depletion potential (ODP) is 0. Many countries have
approved of and encouraged R410A for use as an alternate refrigerant.
• To prevent the refrigerant cylinder from exploding, do not place it in direct sunlight.
• Do not use any piping that has not been approved for use in high-pressure refrigerant systems.
Electrical