EQUIPMENT SELECTION PROCEDURE
Cooling/Heating Correction Factors
For Single Zone Art Cool Premier systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, de-
termine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction
factors as shown in the table below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity tables using
design conditions. The resultant is the NET cooling or heating capacity.
Table 27: Single Zone Wall Mounted Art Cool Premier Cooling/Heating % Coefcient Factors.
Model Main Piping Length
Indoor Unit Outdoor Unit Feet 24.6 32.8 49.2 65.6 82 98.4 114.8 131.2 147.6 164
LAN090HYV1 LAU090HYV1
Cooling 100 98 93 88 - - - - - -
Heating 100 99 96 94 - - - - - -
LAN120HYV1 LAU120HYV1
Cooling 100 98 93 88 - - - - - -
Heating 100 99 96 94 - - - - - -
LAN150HYV2 LAU150HYV2
Cooling 100 100 100 100 100 100 - - - -
Heating 100 98 95 91 88 84 - - - -
LAN180HYV2 LAU180HYV2
Cooling 100 100 100 100 100 100 - - - -
Heating 100 98 95 91 88 84 - - - -
LAN180HYV1 LAU180HVY1
Cooling 100 100 100 100 100 100 - - - -
Heating 100 98 95 91 88 84 - - - -
LAN240HYV1 LAU240HVY1
Cooling 100 100 100 100 100 100 - - - -
Heating 100 98 95 91 88 84 - - - -