Owner's Manual

1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that
satisfies the following conditions.
• The place shall easily bear a load exceeding
four times the indoor unit’s weight.
• The place shall be able to inspect the unit as
the figure.
• T he place where the unit shall be leveled.
• The place shall allow easy water
drainage.(Suitable dimension “H” is necessary
to get a slope to drain as figure.)
•The place shall easily connect with the
outdoor unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will
be good .
• There should not be any heat source or steam
near the unit
2) Outdoor unit
• I f an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful
that heat radiation from the condenser is not
restricted.
• There should not be any animals or plants
which could be affected by hot air
discharged.
• Ensure the spaces indicated by arrows from
the wall, ceiling, fence or other obstacles.
3) Piping length and the elevation
5
Indoor unit
Outdoor unit
B
A
H
1000600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
2. Installation of Indoor, Outdoor Unit
Capacity
Gas
Liquid
Elevation B(m)
Length A(m)
*Additional
refrigerant
(g/m)
Pipe Size
(Diameter : Ø)
Standard Standard
Max.
Max.
66K BTU/h
70
7/8" 1/2"
7.5 5
30 10
Indoor
Unit
(nos)
Outdoor
Unit
(nos)
1 1
• Capacity is based on standard length and maximum allowance
length is on the basis of reliability.