Ceiling Cassette & High Static Ducted Indoor & Outdoor Units
Part 4 Trouble Shooting
- 61 -
Copyright ©2012 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Check Point
1. Check the WCN_P(L),P(N) Connection condition at the Main PCB.(Refer to outdoor wiring diagram)
2. Check the DC Link voltage at not operating(280V
↑
)
3. Check the DC Link voltage at Comp operating(340V
↑
)
4. Check DC Link Sensing Signal :2.4~2.8V (Refer the Picture)
IN/I
GND
<CT Sensing Check Point>
Black
Red
Vdc
* AUUW18GD2[LUU187HV] / AUUW24GD2[LUU247HV]