Engineering and Specifications Manual

50
Indoor Model H/P Inverter #
LMDN095HV
LMDN125HV LMDN185HV
Performance
Capacity* (BTU/h)
9,000 Class
12,000 Class 18,000 Class
Fan Air Flow Rate (CMM)
8.5/7.5/6.5
9.5/8.5/7.5 15.0/13.5/11.5
(H/M/L) (CFM)
300/265/229
335/300/265 530/477/406
Dehumidication Rate (pts/hr)
2.1
2.5 4.2
Sound Level H/M/L (dB(A)*)
32/26/25
33/31/26 34/31/29
Electrical
Running Current (A)
0.25
0.25 0.25
Power Supply (Ø/V/Hz)
1/208~230/60
1/208~230/60 1/208~230/60
Piping Connections
Liquid (inches)
1/4
1/4 1/4
Gas (inches)
3/8
3/8 1/2
Temperature Sensor
Thermistor
Thermistor Thermistor
Refrigerant
R-410A
R-410A R-410A
Power/Transmission Interunit Cable
(No. x AWG)
4 x 18 4 x 18 4 x 18
Dimensions (WxHxD)
Body (inches)
32 9/32 x 7 15/32 x 22 5/8
32 9/32 x 7 15/32 x 22 5/8 43 5/16 x 7 15/32 x 22 5/8
Decorative Panel (inches) - - -
Net Weight Body (lbs) 45.2 45.2 58.4
Net Weight Decorative Panel (lbs) - - -
Limited warranty: 2 years parts
9,000-18,000 BTU/h
Multi F Ceiling
Concealed Duct
Indoor Units
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 80ºF (26.7ºC ) DB/67ºF (19.4ºC) WB
- Outdoor Temperature 95ºF (35ºC) DB/75ºF (23.9ºC) WB
Heating: - Indoor Temperature 70ºF (21.1ºC) DB/60ºF (15.6ºC) WB
- Outdoor Temperature 47ºF (8.3ºC) DB/43ºF (6.1ºC) WB
Piping Length: - Interconnecting Piping Length 24.6 ft.(7.5m)
- Level Difference of Zero
2. Wiring cable size must comply with applicable local and national codes.
3. The specification may be subject to change without prior notice for purpose of
improvement.
4. For more capacity(*) information, refer to the combination tables.
FEATURES:
LMDN095HV (H/P Model)
LMDN125HV (H/P Model)
LMDN185HV (H/P Model)
• Inverter (Variable speed fan)
• Drain pump
• Control lock function
Auto operation
Auto restart operation
• 2 thermistor control
Interior Unit Includes:
• Ceiling unit
Wired remote control
• Owner’s manual
ETL#: 3091879
*LG veried sounds ratings
* Specification can be changed without notification