Multi F Engineering Manual

*HQHUDO'DWD6SHFL¿FDWLRQV
TWO-WAY VAHU INDOOR UNITS
Model Name LMVN240HV LMVN360HV
Nominal Cooling Capacity (Btu/h)
1
24,000 36,000
Nominal Heating Capacity (Btu/h)
1
27,000 40,000
Operating Range
&RROLQJ):%
57-77 57-77
Heating (°F DB)
59-81 59-81
)DQ
Type
Sirocco Sirocco
0RWRU2XWSXW:[4W\
96 x 1 182 x 1
Motor/Drive
Brushless Digitally Controlled / Direct Brushless Digitally Controlled / Direct
$LUIORZ5DWH&)0+0/DW:*(63
710 / 640 / 480 990 / 880 / 800
0D[LPXP([WHUQDO6WDWLF3UHVVXUHLQ:*
1.00 1.00
Unit Data
Refrigerant Type
2
R410A R410A
Refrigerant Control
EEV EEV
Power Supply V, Ø, Hz
3
208-230, 1, 60 208-230, 1, 60
Rated Amps (A)
0.59 1.12
Sound Pressure Level dB(A) (H/M/L)
4
DW:*(63
43 / 42 / 41 45 / 44 / 43
'LPHQVLRQV:[+['LQ
18 x 48-21/32 x 21-1/4 18 x 48-21/32 x 21-1/4
1HW:HLJKWOEV
117 121
6KLSSLQJ:HLJKWOEV
130 135
3RZHU:LULQJ&RPPXQLFDWLRQV&DEOH1R[$:*
5
4 x 18 4 x 18
Heat Exchanger
(Row x Column x Fin / inch) x Number
(2 x 24 x 18) x 2 (3 x 24 x 18) x 2
3LSLQJ
Liquid (in.)
1/4 3/8
Vapor (in.)
1/2 5/8
Primary Drain I.D. (in.)
3/4 FPT 3/4 FPT
Secondary Drain I.D. (in.)
3/4 FPT 3/4 FPT
7DEOH Multi F Vertical-Horizontal Air Handling Indoor Unit General Data.
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and
indoor units. All capacities are net with a combination ratio between 95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
ZHWEXOE:%DQGRXWGRRUDPELHQWFRQGLWLRQVRI)GU\EXOE'%DQG)ZHWEXOE:%
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
ZHWEXOE:%DQGRXWGRRUDPELHQWFRQGLWLRQVRI)GU\EXOE'%DQG)ZHWEXOE:%
2
This unit comes with a dry helium charge.
3
$FFHSWDEOHRSHUDWLQJYROWDJH99
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
5
$OOSRZHUZLULQJFRPPXQLFDWLRQVFDEOHWRWKH,'8VPXVWEHPLQLPXP$:*FRQGXFWRUVWUDQGHG
shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
applicable local and national codes.
VERTICAL-HORIZONTAL | 139
Vertical-Horizontal Air Handling
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
MULTI
F
MAX
MULTI
F