Multi F Engineering Manual

Model No. /
Nominal Capacity
of Indoor Unit
(Btu/h)
Outdoor Air Temp. Indoor Air Temp. °F DB
°F DB ):%
61 64 68 70 72 75
TC TC TC TC TC TC
LVN360HV4
36,000
0 -0.4 20.58 20.29 20.10 20.00 19.71 18.84
5 4.5 23.19 22.90 22.71 22.61 22.32 21.45
10 9 25.80 25.51 25.31 25.22 24.93 24.06
17 15 29.28 28.99 28.79 28.70 28.41 27.48
20 19 30.58 30.29 30.10 30.00 29.71 28.70
25 23 32.75 32.46 32.27 32.17 31.88 30.72
30 28 34.64 34.35 34.15 34.06 33.77 32.75
35 32 36.52 36.23 36.04 35.94 35.65 34.78
40 36 38.21 37.92 37.73 37.63 37.34 36.47
45 41 39.90 39.61 39.42 39.32 39.03 38.16
47 43 40.58 40.29 40.10 40.00 39.71 38.84
50 46 41.23 40.94 40.75 40.65 40.36 39.38
55 51 42.32 42.03 41.84 41.74 41.45 40.29
60 56 42.32 42.03 41.84 41.74 41.45 40.47
63 59 42.32 42.03 41.84 41.74 41.45 40.58
68 64 42.32 42.03 41.84 41.74 41.45 40.76
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
1RPLQDOKHDWLQJFDSDFLW\UDWLQJREWDLQHGZLWKDLUHQWHULQJWKHLQGRRUXQLWDW)GU\EXOE'%DQG)ZHWEXOE:%DQGRXWGRRUDPELHQWFRQGLWLRQVRI)GU\EXOE'%DQG)ZHWEXOE:%
7DEOH0XOWL)9HUWLFDO+RUL]RQWDO$LU+DQGOLQJ,QGRRU8QLWV+HDWLQJ&DSDFLW\7DEOHFRQWLQXHG
FOUR-WAY VAHU INDOOR UNITS
Heating Capacity Table
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
164 | VERTICAL-HORIZONTAL
Multi F and Multi F MAX Indoor Unit Engineering Manual