Product Data

54 | INTRODUCTION
Four-Way Ceiling Cassette System Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ASHRAE Standards 62.1 and 62.2 (depending on if the building is residential or commercial), and local codes specify the minimum volume
of airflow that must be provided to an occupied space. Outdoor air is required to minimize adverse health effects, and it provides acceptable
indoor air quality for building occupants. Indoor units located within the zone typically require less airflow to condition the space. During the
design phase, refer to the airflow capabilities listed in the specification tables for each product. Choose the best method for the application
out of the five (5) ventilation options available.
Disclaimer
Although we believe that these building ventilation methods have been portrayed accurately, none of the methods have been tested, veried, or evalu-
ated by LG Electronics, U.S.A., Inc., In all cases, the designer, installer, and contractor should understand if the suggested method is used, it is used
at their own risk. LG Electronics U.S.A., Inc., takes no responsibility and offers no warranty express, implied, or statutory and the implied warranties of
merchantability and tness for a particular purpose are excluded should the building ventilation methods fail to perform as stated or intended.
For a complete copy of ASHRAE Standard 62.1 and 62.2, refer to the American Standard of Heating and Air Conditioning Engineers (ASHRAE)
website at www.ashrae.org.
Method 1: Natural Ventilation (Non-Ducted, Unconditioned Outdoor Air)
Natural ventilation devices, such as operable windows or louvers may be used to ventilate the building when local code permits. The open
area of a window or the free area of a louver must meet the minimum percentage of the net occupied floor area.
Advantages
Occupants control the volume of the ventilation air manually.
Useful for historic buildings that have no ceiling space available for
outdoor air ductwork.
May be used with the full lineup of Duct-Free Split system indoor
units.
Disadvantages
In some locations, it may be difficult to control humidity levels when
windows are open.
Thermal comfort levels may be substandard when windows are
open.
Indoor units may have to be oversized to account for the added
heating and cooling loads when windows are open.
Provides outdoor air to perimeter spaces only. Additional mechan-
ical ventilation system may be required to satisfy requirements for
interior spaces.
Outdoor air loads may be difficult to calculate since the quantity of
outdoor air is not regulated.
May affect indoor unit proper operation when open.
Figure 31: Natural Ventilation (Non-Ducted, Unconditioned Outdoor Air).
BUILDING VENTILATION DESIGN GUIDE
Methodology illustrations are for examples only and do not depict actual
indoor units for the specic outdoor unit pairing. These are generic illus-
trations to show ventilation design only.
Indoor units (IDUs) should not be placed in an environment where the IDUs may be exposed to harmful volatile organic compounds (VOCs) or in
environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the environment where the
IDUs are installed, proper air make up or supply and/ or adequate ventilation should be provided. Additionally, in buildings where IDUs will be exposed
to VOCs consider a factory-applied epoxy coating to the fan coils for each IDU.