Install Instructions

3) Insulation tube thickness
Thickness decision of insulation tube
• Insulation material: EPDM or polyethylene foam
• Thermal conductivity 0.035 kcal~0.040kcal/m·h°C(0.024~0.027Btu/ft·h℉)
• Heat resistance = 212°F(Cooling only) or more
248°F(Heat pump) or over
The thickness of the thermal insulation material must be determined in the light of the pipe sizes.
It will be necessary to increase the thickness of insulation in the above table when conditions are hot and humid.
Where a customer supplies his own specifications then these must be adhered to.
Pipe size Thickness of insulation material
6.35(1/4) ~ 25.4(1) mm(inch) 10(13/32) mm(inch) or more
25.4(1) mm(inch) ~ 15(19/32) mm(inch)
Outdoor temperature and hummidity around the cooling piping might exceed 86°F and RH80%, reinforce the insulation
on the cooling piping (at least 13/16 inch thick)
CAUTION
2. Guideline for each installation process
22 _ Heat pump 60Hz/R410A
Installation of
Outdoor Units
SINGLE ZONE