Installation Manual

26 Air Conditioner
Indoor Unit Drain Piping
CAUTION :The supplied
flexible drain hose should not
be curved, neither screwed.The
curved or screwed hose may
cause a leakage of water.
Connect the main drain pipe to the exterior and
leave it provisionally until the test comes to an
end.
Feed water to the flexible drain hose and check
the piping for leakage.
Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
When the test is complete, connect the flexible
drain hose to the drain port on the indoor unit.
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Drain test
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
1/50~1/100
Flexible drain hoseFlexible drain hose
[Cassette Type]
Drain piping must have down-slope (1/50 to 1/100): be
sure not to provide up-and-down slope to prevent
reversal flow.
During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
The outside diameter of the drain connection on the
indoor unit is 32mm(1 1/4 inch).
Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe inner
diometes Ø 25mm(1 inch) and pipe fittings
Heat insulation material: Polyethylene foam
with thickness more than 8mm(5/16 inch).
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX : 800mm
(32-1/2 inch)