Installation Manual
Installation of Indoor, Outdoor Unit
Installation Manual 9
ENGLISH
3. Piping length and the elevation
24k Btu/h
15.88(5/8) 9.5(3/8)
7.5(25) 5(16) 35(0.38)
Gas Liquid Standard Max. Standard Max
.
Capacity
Pipe Size Length A Elevation B
*Additional
Unit : mm(inch) Unit : m(ft) Unit : m(ft)
refrigerant
Unit : g/m(oz/ft)
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION:
• Rated performance for refrigerant line length of:7.5m(25ft)
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters(32.8 ft).
50(164)
cassette type
30(98)
Floor standing type
30(98)
cassette type
20(66)
Floor standing type