Multi F Outdoor Unit Data
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Table 16: LMU18CHV with Non-Ducted, Ducted, and Mixed Indoor Units — Rated Cooling Combination Table.
No. of
Indoor
Units
Indoor Unit Combination
(kBtu/h)
Room Capacity Total Capacity Input (W)
EER SEER
IDU
1
IDU
2
IDU
3
IDU
4
Total
Unit 1
(Btu/h)
Unit 2
(Btu/h)
Unit 3
(Btu/h)
Unit 4
(Btu/h)
Minimum Rated Maximum
Min. Rated Max.
Btu/h kW Btu/h kW Btu/h kW
Non-Ducted Indoor Units
Two
Units
7 7 - - 14 7,000 7,000 - - 8,400 2.46 14,000 4.10 16,800 4.92 826 1,180 1,652 11.9 20.1
7 9 - - 16 7,000 9,000 - - 9,600 2.81 16,000 4.69 19,000 5.57 868 1,240 1,736 12.9 21.9
9 9 - - 18 8,500 8,500 - - 10,200 3.16 17,000 4.98 19,000 5.57 917 1,310 1,834 13.0 22.0
7 12 - - 19 6,263 10,737 - - 10,200 2.99 17,000 4.98 19,000 5.57 917 1,310 1,834 13.0 22.0
9 12 - - 21 7,286 9,714 - - 10,200 3.16 17,000 4.98 19,000 5.57 917 1,310 1,834 13.0 22.0
7 15 - - 22 5,409 11,591 - - 10,200 2.99 17,000 4.98 19,000 5.57 917 1,310 1,834 13.0 22.0
9 15 - - 24 6,375 10,625 - - 10,200 2.99 17,000 4.98 19,000 5.57 917 1,310 1,834 13.0 22.0
12 12 - - 24 8,500 8,500 - - 10,200 3.16 17,000 4.98 19,000 5.57 917 1,310 1,834 13.0 22.0
Ducted Indoor Units
Two
Units
9 9 - - 18 7,000 7,000 - - 8,400 3.16 14,000 4.10 19,000 5.57 916 1,308 1,831 10.7 17.2
9 12 - - 21 6,000 8,000 - - 8,400 3.16 14,000 4.10 19,000 5.57 916 1,308 1,831 10.7 17.2
12 12 - - 24 7,000 7,000 - - 8,400 3.16 14,000 4.10 19,000 5.57 916 1,308 1,831 10.7 17.2
Mixed Indoor Units
Two
Units
7 9 - - 16 6,382 8,206 - - 8,753 2.57 14,588 4.28 19,000 5.57 867 1,239 1,735 11.8 19.5
9 9 - - 18 7,750 7,750 - - 9,300 3.16 15,500 4.54 19,000 5.57 916 1,309 1,833 11.8 19.6
7 12 - - 19 5,711 9,789 - - 9,300 2.73 15,500 4.54 19,000 5.57 916 1,309 1,833 11.8 19.6
9 12 - - 21 6,643 8,857 - - 9,300 3.16 15,500 4.54 19,000 5.57 916 1,309 1,833 11.8 19.6
9 15 - - 24 5,813 9,688 - - 9,300 2.73 15,500 4.54 19,000 5.57 916 1,309 1,833 11.8 19.6
12 12 - - 24 7,750 7,750 - - 9,300 3.16 15,500 4.54 19,000 5.57 916 1,309 1,833 11.8 19.6
Rated Cooling Combination Tables
PERFORMANCE DATA
1
Capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
2
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
3
Wiring cable size must comply with the applicable local and national codes.
4
The specification may be subject to change without prior notice for purpose of improvement.
5
At least two indoor units should be connected.