28 | MULTI F OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual
MULTI
F
MAX
MULTI
F
Rated Cooling Combination Tables
PERFORMANCE DATA
No. of
Indoor
Units
Indoor Unit Combination
(kBtu/h)
Room Capacity Total Capacity Input (W)
EER SEER
IDU
1
IDU
2
IDU
3
IDU
4
Total
Unit 1
(Btu/h)
Unit 2
(Btu/h)
Unit 3
(Btu/h)
Unit 4
(Btu/h)
Minimum Rated Maximum
Min. Rated Max.
Btu/h kW Btu/h kW Btu/h kW
Ducted Indoor Units
Two
Units
9 9 - - 18 7,875 7,875 - - 9,450 2.8 15,750 4.6 17,483 5.1 1,245 1,779 2,491 8.9 14.6
9 12 - - 21 7,875 10,500 - - 11,025 3.2 18,375 5.4 20,396 6.0 1,426 2,038 2,853 9.0 14.9
12 12 - - 24 10,500 10,500 - - 12,600 3.7 21,000 6.2 23,310 6.8 1,578 2,255 3,157 9.3 15.4
9 18 - - 27 7,875 15,750 - - 14,175 4.2 23,625 6.9 26,224 7.7 1,752 2,503 3,504 9.4 15.6
12 18 - - 30 10,500 15,750 - - 15,750 4.6 26,250 7.7 29,138 8.5 1,904 2,720 3,808 9.6 16.0
9 24* - - 33 7,636 20,364 - - 16,800 4.9 28,000 8.2 31,080 9.1 1,998 2,855 3,997 9.8 16.2
18 18 - - 36 14,000 14,000 - - 16,800 4.9 28,000 8.2 31,080 9.1 1,998 2,855 3,997 9.8 16.2
12 24* - - 36 9,333 18,667 - - 16,800 4.9 28,000 8.2 31,080 9.1 1,998 2,855 3,997 9.8 16.2
Three
Units
9 9 9 - 27 7,875 7,875 7,875 - 14,175 4.2 23,625 6.9 27,169 8.0 1,665 2,379 3,331 9.9 16.4
9 9 12 - 30 7,875 7,875 10,500 - 15,750 4.6 26,250 7.7 30,188 8.8 1,781 2,544 3,562 10.3 17.1
9 12 12 - 33 7,636 10,182 10,182 - 16,800 4.9 28,000 8.2 32,200 9.4 1,868 2,669 3,736 10.5 17.4
9 9 18 - 36 7,000 7,000 14,000 - 16,800 4.9 28,000 8.2 32,200 9.4 1,868 2,669 3,736 10.5 17.4
12 12 12 - 36 9,333 9,333 9,333 - 16,800 4.9 28,000 8.2 32,200 9.4 1,868 2,669 3,736 10.5 17.4
9 12 18 - 39 6,462 8,615 12,923 - 16,800 4.9 28,000 8.2 32,200 9.4 1,868 2,669 3,736 10.5 17.4
12 12 18 - 42 8,000 8,000 12,000 - 16,800 4.9 28,000 8.2 32,200 9.4 1,868 2,669 3,736 10.5 17.4
9 18 18 - 45 5,600 11,200 11,200 - 16,800 4.9 28,000 8.2 32,200 9.4 1,868 2,669 3,736 10.5 17.4
12 18 18 - 48 7,000 10,500 10,500 - 16,800 4.9 28,000 8.2 32,200 9.4 1,868 2,669 3,736 10.5 17.4
Four
Units
9 9 9 9 36 7,000 7,000 7,000 7,000 16,800 4.9 28,000 8.2 33,600
9.8 1,782 2,545 3,564 11.0 18.2
9 9 9 12 39 6,462 6,462 6,462 8,615 16,800 4.9 28,000 8.2 33,600 9.8 1,782 2,545 3,564 11.0 18.2
9 9 12 12 42 6,000 6,000 8,000 8,000 16,800 4.9 28,000 8.2 33,600 9.8 1,782 2,545 3,564 11.0 18.2
9 9 9 18 45 5,600 5,600 5,600 11,200 16,800 4.9 28,000 8.2 33,600 9.8 1,782 2,545 3,564 11.0 18.2
9 12 12 12 45 5,600 7,467 7,467 7,467 16,800 4.9 28,000 8.2 33,600 9.8 1,782 2,545 3,564 11.0 18.2
9 9 12 18 48 5,250 5,250 7,000 10,500 16,800 4.9 28,000 8.2 33,600 9.8 1,782 2,545 3,564 11.0 18.2
12 12 12 12 48 7,000 7,000 7,000 7,000 16,800 4.9 28,000 8.2 33,600 9.8 1,782 2,545 3,564 11.0 18.2
Table 21: LMU36CHV with Ducted Indoor Units — Rated Cooling Combination Table.
1
Capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
2
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
3
Wiring cable size must comply with the applicable local and national codes.
4
The specification may be subject to change without prior notice for purpose of improvement.
5
At least two indoor units should be connected.
*A 1.3 multiplier is necessary for the calculation of total combination.