Design pressure is 551 psig.
$OOGLPHQVLRQVLQLQFKHV7ROHUDQFHLQFK
Images are not to scale.
REFRIGERANT PIPING DESIGN
LG Engineered Multi F MAX Y-Branch Kit
The LG supplied Y-Branch Kit PMBL5620 MUST be used when two
branch distribution units are connected on one Multi F MAX system.
Field-supplied fittings are not permitted. Each Y-Branch kit comes
with two (2) Y-branches (one for the liquid line and one for the vapor
line) and insulation covers.
Y-branches may be installed in horizontal or vertical configurations.
When installed vertically, position the Y-branch so the straight-
through leg is ±3° of plumb. When installed horizontally, position the
Y-branch so the take-off leg is level and shares the same horizontal
plane as the straight-through leg ±10° rotation.
Y-branches must be properly installed following instructions in the
applicable LG manual. Y-branches should always be installed with
the single port facing the outdoor unit and the two-port end facing
the branch distribution units. Do not install Y-branches backwards
as refrigerant flow cannot make U-turns. The Y-branch kit must be
located at least three (3) feet from the outdoor unit. Provide
a minimum of 20 inches between a Y-branch and the branch
distribution unit.
It is recommended that when a Y-branch is located in a pipe chase
or other concealed space, access doors should be provided for
inspection access.
7KHHTXLYDOHQWSLSHOHQJWKRIHDFK<EUDQFKƍPXVWEHDGGHGWR
the main pipe segment entered into LATS piping design software.
Figure 252: Y-Branch Connections.
Figure 253: Y-Branch Dimensions Diagram.
Figure 254: +RUL]RQWDO&RQ¿JXUDWLRQ(QG9LHZ
Multi F MAX Y-Branch Kit PMBL5620
Table 103: Y-Branch Connection Diameters.
Model
Y-Branch
Type
3RUW,GHQWL¿HULQFK Dimensions
123XY
PMBL5620
Liquid 3/8 3/8 3/8 13.80 3.24
Vapor 3/4 3/4 3/4 12.48 3.02
To Branch Distribution Unit Ø3/4
Ø3/4
To Outdoor Unit
Ø3/4
Ø3/8
Ø3/8
To Outdoor Unit
To Branch Distribution Unit Ø3/8
Y-Branch Kit Insulation
Each Y-branch kit comes with clam-shell type peel-and-stick insula-
tion jackets molded to fit the Y-branch fittings—one for the liquid
line, one for the vapor line.
Check the fit of the Y-branch clam-shell insulation jacket after the
Y-branch is installed.
Mark the pipe where the insulation jacket ends.
Remove the jacket.
Install field-provided insulation on the pipes first.
Peel the adhesive glue protector slip and install the clam-shell
jacket over the fitting
Figure 255: <EUDQFK,QVWDOODWLRQ$OLJQPHQW6SHFL¿FDWLRQ
Viewed from A in direction of arrow
Horizontal
plane
Within ±5
°
A
Vertical Up Configuration
Within ± 3°Within ± 3°
Vertical Down Configuration
Liquid and Gas
Pipe Joints
Y-Branch Kit Insulation
Insulation for
Field-Installed Piping
Field-Supplied Insulation Tape
A
B
X
Y
1
2
3
A = To Outdoor Unit
B = To Branch
Distribution Unit
Figure 256: Y-branch Insulation Detail.
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
DESIGN & PRACTICES | 191
Refrigerant Piping Design and Best Practices