Brochure
19
LG Air Conditioning Technologies
Specification Unit
LH248HV4 LH368HV4
Indoor Unit
LHN248HV LHN368HV
Outdoor Unit
LUU249HV LUU369HV
Capacity
Rated Cooling Capacity Btu/h
24,000 36,000
Cooling Capacity Range Btu/h
9,600 ~ 27,000 14,400 ~ 41,400
Rated Heating Capacity Btu/h
27,000 40,000
Heating Capacity Range Btu/h
10,800 ~ 30,000 16,000 ~ 42,200
Max Heating Capacity at 17°F Btu/h
26,000 41,500
Max Heating Capacity at 5°F Btu/h
23,600 35,000
SEER, EER
19.0, 12.0 19.0, 12.1
HSPF
10.5 9.7
Power
Voltage (IDU) V, Ø, Hz
208/230-1-60 208/230-1-60
Voltage (ODU) V, Ø, Hz
208/230-1-60 208/230-1-60
Cooling Power Input kW
2.98 2.98
Heating Power Input kW
2.08 3.08
MCA, MOCP A
20, 30 32, 40
Power/Communication Wiring
4
No. x AWG
4 x 14 4 x 14
Rated Amps Cool/Heat A
16.7/16.7 27.5/27.5
Operating Range
Heating Operation Range °F WB
-4 ~ 64 -4 ~ 64
Cooling Operation Range °F DB
5 ~ 118 5 ~ 118
Optional Wind Baffle
6
ZLABGP04A (-4˚F) ZLABGP04A x 2 (-4˚F)
IDU Operation Range Cooling °F WB
57 ~ 77 57 ~ 77
IDU Operation Range Heating °F DB
59 ~ 81 59 ~ 81
Setpoint Range Cooling °F
65 ~ 86 65 ~ 86
Setpoint Range Heating °F
61 ~ 86 61 ~ 86
Dimensions
IDU Dimensions (WxHxD) in
35-1/2 x 10-11/16 x 27-1/4 49-9/32 x 10-11/16 x 27-1/4
ODU Dimensions (WxHxD) in
37-13/32 x 32-27/32 x 13 37-19/32 x 54-11/32 x 13
Weight
IDU Weight (Net/Shipping) lbs
58.6 / 71.9 85.3 / 99.4
ODU Weight (Net/Shipping) lbs
130.0 / 143.3 198.9 / 223.1
Unit Data
Airflow (Max/H/M/L)
7
CFM
777/706/636 1,130/989/848
Dehumidification pts/hr
5.1 5.9
Compressor Type
Twin Rotary x 1 Scroll x 1
Refrigerant Type
R410A R410A
Max External Static Pressure
in wg 0.24 0.24
Sound Pressure
Indoor (H/M/L) dB(A)
37 / 35 / 34 44 / 42 / 40
Outdoor Max (Cool / Heat) dB(A)
48 / 52 52 / 54
Piping
Liquid Pipe in
3/8 3/8
Vapor Pipr in
5/8 5/8
Pipe Length (Min/Max) ft
24.6/164 24.6/246.1
Max Pipe Elevation ft
98.4 98.4
Precharge Pipe Length ft
24.6 24.6
Additional Refrigerant oz/ft
0.43 0.43
Drain (OD, ID) in
1.25/1 1.25/1
Controller
Additional Accessory
9
Wired Controller Wired Controller
LH248HV4
LH368HV4
HIGH STATIC DUCTED
Note:
1. Rated capacity at 0 ft. above sea level with 25 ft. of refrigerant line and a 0 ft. level difference between outdoor and indoor unit.
2. Rated cooling capacity obtained with air entering the indoor unit at 80˚F dry bulb (DB) and 67˚F wet bulb (WB) and outdoor ambient conditions of 95˚F dry bulb (DB) and 75˚F wet bulb (WB).
Rated heating capacity obtained with air entering the indoor unit at 70˚F dry bulb (DB) and 60˚F wet bulb (WB) and outdoor ambient conditions of 47˚F dry bulb (DB) and 43˚F wet bulb (WB).
For capacity information, see engineering manual capacity tables.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the same in both cooling and heating mode. These values can increase due to ambient conditions during operation.
4. All power/communication wiring minimum 4-conductor, stranded, shielded, and must comply with applicable local and national codes.
5. Piping lengths are equivalent.
6. Installation of an optional Low Ambient Wind Baffle Kit will allow operation down to 0˚F in cooling mode for applicable outdoor units.
7. Airflow shown is in cooling mode.
8. Due to our commitment to continued innovation, some specifications may be changed without notification.
9. All LG wired controls are compatible and can be considered for control.