Brochure

25
LG Air Conditioning Technologies
Multi-Zone
Specication Unit LMU480HV LMU540HV LMU600HV
Capacity
Rated Cooling Capacity Btu/h
48,000 52,500 60,000
Cooling Capacity Range Btu/h
14,400 ~ 58,000 14,400 ~ 63,200 15,600 ~ 68,000
Rated Heating Capacity Btu/h
54,000 58,000 64,000
Heating Capacity Range Btu/h
15,840 ~ 61,000 16,272 ~ 64,000 17,940 ~ 70,000
Max Heating Capacity at 17˚F Btu/h
49,014 51,832 53,560
Max Heating Capacity at 5˚F Btu/h
38,900 41,137 42,720
Max Heating Capacity at -4˚F Btu/h
27,529 29,112 33,193
SEER, EER
5
19.5, 12.5 18.4, 10.3 20.5, 11.4
HSPF
5
10.0 8.7 11
Power
Voltage V, Ø, Hz
208/230-1-60 208/230-1-60 208/230-1-60
Cooling Power Input kW
3.84 5.1 5.26
Heating Power Input kW
4.32 5.4 5.33
MCA, MOCP A
27.3, 40 29.4, 40 32.2, 45
Rated Amps (Cool/Heat) A
22.96/22.96 24.76/24.76 27.06/27.06
Power/Communication Wiring
4
No. x AWG
ODU --> BDU: 4 x 14 BDU --> IDU: 4 x 14 ODU --> BDU: 4 x 14 BDU --> IDU: 4 x 14 ODU --> BDU: 4 x 14 BDU --> IDU: 4 x 14
Operating Range
Heating Operation Range °F WB
-4 ~ 64 -4 ~ 64 -4 ~ 64
Cooling Operation Range °F DB
14 ~ 118 14 ~ 118 14 ~ 118
Optional Wind Bafe
7
ZLABGP04A x 2 (-4˚F) ZLABGP04A x 2 (-4˚F) ZLABGP04A x 2 (-4˚F)
Dimensions & Weight
Dimensions (WxHxD) in
37-13/32 × 54-11/32 × 13 37-13/32 × 54-11/32 × 13 37-13/32x54-11/32x13
Weight (Net/Shipping) lbs
214/236 214/236 223/249
Unit Data
Refrigerant Type
R410A R410A R-410A
Compressor Type
Twin Rotary Twin Rotary Twin Rotary
Sound Pressure (Cooling / Heating) dB(A)
54/56 54/56 56/58
Maximum Air Volume CFM
2,119 x 2 2,119 x 2 2,119 x 2
Minimum Connectable IDUs Qty
2 2 2
Maximum Connectable IDUs Qty
8 8 8
Max Total IDU Connected Capacity Btu/h
65,000 73,000 81,000
Piping
Liquid Pipe in
3/8 3/8 3/8
Vapor Pipe in
3/4 3/4 3/4
Maximum Total Pipe Length ft
475.7 475.7 475.7
Minimum Pipe Length per Segment ft
9.8 9.8 9.80
Maximum Pipe Length ODU to IDU ft
229.6 229.6 229.6
Maximum Main Pipe Length ft
180.4 180.4 180.4
Precharge Pipe Length ft
Main: 16.4
Branch: 131.2
Main: 16.4
Branch: 131.2
Main: 16.4
Branch: 131.2
Maximum Elevation ODU to IDU ft
98.4 98.4 98.4
Maximum Elevation IDU to IDU ft
49.2 49.2 49.2
Maximum Elevation BDU to IDU ft 32.8 32.8 38.2
Maximum Elevation BDU to BDU ft 49.2 49.2 49.2
Factory Charge of R410A lbs
9.7 9.7 12.3
Additional Refrigerant oz/ft
Main: 0.54
Branch: 0.22
Main: 0.54
Branch: 0.22
Main: 0.54
Branch: 0.22
MULTI F MAX OUTDOOR UNITS
LMU480HV
LMU540HV
LMU600HV
Note:
1. Rated capacity at 0 ft. above sea level with 25 ft. of refrigerant line and a 0 ft. level difference between outdoor and indoor unit.
2. Rated cooling capacity obtained with air entering the indoor unit at 80˚F dry bulb (DB) and 67˚F wet bulb (WB) and outdoor ambient conditions of 95˚F dry bulb (DB) and 75˚F wet bulb (WB).
Rated heating capacity obtained with air entering the indoor unit at 70˚F dry bulb (DB) and 60˚F wet bulb (WB) and outdoor ambient conditions of 47˚F dry bulb (DB) and 43˚F wet bulb (WB).
For capacity information, see engineering manual capacity tables. Capacities are based on connection of Non-Ducted indoor units.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the same in both cooling and heating mode. These values can increase due to ambient conditions during operation.
4. All power/communication wiring minimum 4-conductor, stranded, shielded, and must comply with applicable local and national codes.
5. Values when matched with non-ducted units only.
6. Piping lengths are equivalent.
7. Installation of an optional Low Ambient Wind Baffle Kit will allow operation down to -4˚F in cooling mode for applicable outdoor units.