Brochure
30
High Static Ducted
Specification Unit LHN248HV LHN368HV
Capacity
Cooling Btu/h 24,000 36,000
Heating Btu/h 27,000 40,000
Power
Voltage V, Ø, Hz 208/230-1-60 208/230-1-60
Power/Communication Wiring
4
No. x AWG 4 x 14 4 x 14
Operating Range
Cooling °F WB 57 ~ 77 57 ~ 77
Heating °F DB 59 ~ 81 59 ~ 81
Fan
Type Sirocco Sirocco x 2
Motor Output x Qty W 136.5 x 1 259 x 1
Motor/Drive BLDC BLDC
Airow (H/M/L) CFM 777/706/636 1,130/989/848
Unit Data
Rated Amps A 1.6 2.3
Factory Set External Static Pressure in. wg 0.24 0.24
Max. External Static Pressure in. wg 0.59 0.59
Sound Pressure Level (H/M/L)
3
dB(A) 37/35/34 44/42/40
Dimensions (WxHxD) in 35-7/16 x 10-5/8 x 27-9/16 49-3/16 x 10-5/8 x 27-9/16
Weight (Net/Shipping) lbs 59/72 86/100
Piping
Liquid Pipe in 1/4 3/8
Vapor Pipe in 1/2 5/8
Drain (OD/ID) in 1-1/4, 1 1-1/4, 1
Controller Additional Accessory
6
Wired Controller Wired Controller
MULTI F INDOOR UNITS
Note:
1. Rated capacity at 0 ft. above sea level with 25 ft. of refrigerant line and a 0 ft. level difference between outdoor and indoor unit.
2. Rated cooling capacity obtained with air entering the indoor unit at 80˚F dry bulb (DB) and 67˚F wet bulb (WB) and outdoor ambient conditions of 95˚F dry bulb (DB) and 75˚F wet bulb (WB).
Rated heating capacity obtained with air entering the indoor unit at 70˚F dry bulb (DB) and 60˚F wet bulb (WB) and outdoor ambient conditions of 47˚F dry bulb (DB) and 43˚F wet bulb (WB).
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the same in both cooling and heating mode. These values can increase due to ambient conditions during operation.
4. All power/communication wiring minimum 4-conductor, stranded, shielded, and must comply with applicable local and national codes.
5. All LG wired controls are compatible and can be considered for control.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.
Multi-Zone
• INDOOR UNITS
Vertical AHU
Specication Unit
LVN181HV4 LVN241HV4 LVN361HV4
Capacity
Cooling Btu/h
18,000 24,000 36,000
Heating Btu/h
20,000 27,000 40,000
Power
Voltage V, Ø, Hz
208/230-1-60 208/230-1-60 208/230-1-60
Power/Communication Wiring
5
No. x AWG
4 x 14 4 x 14 4 x 14
Operating Range
Cooling °F WB
57 ~ 77 57 ~ 77 57 ~ 77
Heating °F DB
59 ~ 81 59 ~ 81 59 ~ 81
Fan
Type
Sirocco Sirocco Sirocco
Motor Output x Qty W
250 x 1 250 X 1 250 x 1
Motor/Drive
Constant CFM ECM Constant CFM ECM Constant CFM ECM
Airow (H/M/L) CFM
640/580/480 710/640/480 990/880/800
Unit Data
Rated Amps A
1.1 1.1 1.1
Max. External Static Pressure in. wg
0.7 0.7 0.7
Sound Pressure Level (H/M/L)
4
dB(A)
35/33/30 36/34/30 44/41/39
Dimensions (WxHxD) in
18 x 48-11/16 x 21-1/4 18 x 48-11/16 x 21-1/4 18 x 48-11/16 x 21-1/4
Weight (Net/Shipping) lbs
124/136 124/136 129/140
Piping
Liquid Pipe in
1/4 1/4 3/8
Vapor Pipe in
1/2 1/2 5/8
Drain in
Primary & Secondary: 3/4 FPT Primary & Secondary: 3/4 FPT Primary & Secondary: 3/4 FPT
Controller Additional Accessory
6
Wired Controller Wired Controller Wired Controller