Brochure

31
LG Air Conditioning Technologies
• Distribution of refrigerant to various indoor units
• 4 models (2, 3, 4 indoor units)
• Integral EEVs
• Controlling PCB inside the unit
Internally insulated (prevents condensation)
• Flare joints for easy and clean installation
• Compact design (low height)
• Flexible installation
Distributor Box
Y Branch
For 2 IDUs 3 IDUs 4 IDUs 4 IDUs
Branch Distribution Unit
Y-Branch
PMBD3640 PMBD3641
PMBD3620 PMBD3630
PMBL5620
Specification Unit PMBD3620 PMBD3630 PMBD3640 PMBD3641
Max Nominal
Port Capacity
Each Port Btu/h 24,000 24,000 24,000
Ports A ~ C: 24,000
Port D: 36,000
Sum of Ports Btu/h 48,000 72,000 73,000 73,000
Connectable Indoor Units 1 ~ 2 1 ~ 3 1 ~ 4 1 ~ 4
Operating Range
°F DB 0 ~ 150 0 ~ 150 0 ~ 150 0 ~ 150
Voltage V, Ø, Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Power Input
W
16 24 32 32
Rated Amps
A
0.08 0.12 0.16 0.16
Dimensions WxHxD
inch
17-3/32 x 6-13/32 x
10-23/32
17-3/32 x 6-13/32 x
10-23/32
17-3/32 x 6-13/32 x
10-23/32
17-3/32 x 6-13/32 x
10-23/32
Weight
Net
lbs
13 15 16 16
Shipping
lbs
15 17 18 18
Pipe Connection Size
(In from ODU)
Liquid
in
3/8 3/8 3/8 3/8
Vapor
in
3/4 3/4 3/4 3/4
Pipe Connection Size
(Out to IDU)
Liquid
in
1/4 (x2) 1/4 (x3) 1/4 (x4)
Ports A ~ C: 1/4
Port D: 1/4
Vapor
in
3/8 (x2) 3/8 (x3) 3/8 (x4)
Ports A ~ C: 3/8
Port D: 1/2
Max Pipe Length BD Box to IDU
ft
49.2 49.2 49.2 49.2
Max Pipe Elevation
BD Box to IDU
ft
32.8 32.8 32.8 32.8
BD Box to BD Box
ft
49.2 49.2 49.2 49.2
Note :
1. Branch Distribution Unit should be installed indoors.
2. Due to our commitment to continued innovation, some specifications may be changed without notification.
MULTI F MAX PIPING ACCESSORIES
Accessory Lineup
Branch Distribution Unit Features
Specifications
MULTI F MAX
PIPING ACCESSORIES