Concealed Duct Installation Manual

26
REMOTE CONTROLLER INSTALLATION
ENGLISH
Wired remote controller installation
Since the room temperature sensor is in the remote controller, the remote controller box should
be installed in a place away from direct sunlight, high humidity and direct supply of cold air to
maintain proper space temperature. Install the remote controller about 5 ft(1.5 m) above the floor
in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with LCD. display. For proper display of the remote controller
LCD's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 4~5 ft (1.2~1.5 m) from floor level.)
TEMP
FAN
SPEED
OPER
MODE
TEMP
FAN
SPEED
OPER
MODE
TEMP
FAN
SPEED
OPER
MODE
5 feet
(1.5 meters)
no
no
no
yes
TEMP
FAN
SPEED
OPER
MODE
[Fig.1]
When connecting Terminal Blocks of the indoor C/BOX and the wired remote controller with the
extension cable, refer to the steps below.
Remove the screw on the cable which is fastened to the wired remote controller’s Terminal
Block by loosening with a screw driver.
Remove the housing of the provided 32 ft extension cable with a cutting nipper and peel it as
shown in the figure below. (when purchasing the extension cable at the site directly, please
peel it as shown in the figure below.)
1.378 inch(35 mm)
±0.197 inch(5 mm)
0.394 inch(10 mm) ± 0.118 inch(3 mm)
Signal Yellow
12 V Red
GND Black
<TYPE C>