Concealed Duct Installation Manual

HOW TO SET E.S.P?
ENGLISH
27
Installer Setting - E.S.P.
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
The procedure of setting E.S.P. is refer to the manual of remote controller.
• Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
• E.S.P value can be varied according to the products.
• In the case of going to the next air flow rate stage by pressing the fan-speed button during
the setup of the E.S.P value, the E.S.P value of previous air flow rate will be maintained by
remembering the E.S.P value prior to the shift.
HOW TO SET E.S.P?
(Unit : CMM)
Capacity Step CFM
Static Pressure(mmAq(in.Aq))
0(0) 1(0.04) 2(0.08) 3(0.12) 4(0.16) 5(0.2)
Setting Value
9 k
HIGH 318 98 103 108 116 125 130
MID 247 82 88 94 102 110 118
LOW 194 69 76 83 91 99 109
12 k
HIGH 353 95 99 104 109 116 125
MID 300 86 91 96 101 108 116
LOW 247 78 82 87 93 100 108
18 k
HIGH 530 123 125 129 134 140 145
MID 441 109 112 117 123 129 136
LOW 353 95 99 104 109 116 124
<TYPE A>