Concealed Duct Installation Manual
Table Of Contents
26
HOW TO SET E.S.P?
ENGLISH
Capacity
Step CFM
Static Pressure(mmAq(in.Aq))
2.5(0.1) 4(0.16) 5(0.2) 6(0.24) 7(0.28) 8(0.31) 9(0.35) 10(0.39) 11(0.43) 12(0.47) 13(0.51) 15(0.59)
Setting Value
24 k
HIGH 777 110 117 121 124 127 130 133 136 137 - 138 140
MID 706 102 110 114 118 120 125 127 130 133 - 134 136
LOW 636 96 102 107 110 114 118 122 125 127 - 130 132
36 k
HIGH 1 130 - 109 112 115 119 122 126 128 131 134 137 144
MID 989 - 101 105 108 112 115 119 123 127 130 133 138
LOW 848 - 92 97 101 105 109 113 117 121 124 127 134
42 k
HIGH 1 413 - 83 89 92 94 98 100 102 105 108 110 116
MID 1 200 - 78 82 84 89 94 96 98 101 104 106 112
LOW989 - 747679828992949699102107
48 k
HIGH 1 766 - 94 97 100 104 107 109 112 115 117 119 121
MID 1 589 - 90 92 96 98 102 104 106 109 112 114 117
LOW 1 413 - 82 89 92 94 98 100 102 105 108 110 113