Concealed Duct Installation Manual

26
HOW TO SET E.S.P?
ENGLISH
Capacity
Step CFM
Static Pressure(mmAq(in.Aq))
2.5(0.1) 4(0.16) 5(0.2) 6(0.24) 7(0.28) 8(0.31) 9(0.35) 10(0.39) 11(0.43) 12(0.47) 13(0.51) 15(0.59)
Setting Value
24 k
HIGH 777 110 117 121 124 127 130 133 136 137 - 138 140
MID 706 102 110 114 118 120 125 127 130 133 - 134 136
LOW 636 96 102 107 110 114 118 122 125 127 - 130 132
36 k
HIGH 1 130 - 109 112 115 119 122 126 128 131 134 137 144
MID 989 - 101 105 108 112 115 119 123 127 130 133 138
LOW 848 - 92 97 101 105 109 113 117 121 124 127 134
42 k
HIGH 1 413 - 83 89 92 94 98 100 102 105 108 110 116
MID 1 200 - 78 82 84 89 94 96 98 101 104 106 112
LOW989 - 747679828992949699102107
48 k
HIGH 1 766 - 94 97 100 104 107 109 112 115 117 119 121
MID 1 589 - 90 92 96 98 102 104 106 109 112 114 117
LOW 1 413 - 82 89 92 94 98 100 102 105 108 110 113