Installation Manual

8
INSTALLATION
ENGLISH
Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.
- Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
- Apply a filter Accessory at air return hole.
<TYPE A> <TYPE B/C>
[Unit:mm(inch)]
C
E
G
D
F
I
A
J
B
H
Drainage hole
9 k 12/18 k 24 k / 36 k 24 k 36 k
Model
AMNW**GL*A*
(TYPE A)
AMNW**GBGA0
(TYPE B)
ABNH**GGLA2
(TYPE C)
A
733 (28-17/20) 933 (36-37/50) 1,232 (48-1/2) 1,232 (48.5) 1,290(50.8)
B
772 (30-2/5) 972 (38-13/50) 1,182 (46-17/32) 1,182 (46.5) 1,230(48.4)
C
628 (24-18/25) 628 (24-18/25) 355 (13-31/32) 355 (14) 477(18.8)
D
700 (27-11/20) 700 (27-11/20) 45.5 (1-25/32) 45.5 (1.8) 56(2.2)
E
36 (1-2/5) 36 (1-2/5) 450 (17-23/32) 450 (17.7) 590(23.2)
F
190 (7-12/25) 190 (7-12/25) 30 (1-3/16) 30 (1.2) 30(1.2)
G
20 (25/32) 20 (25/32) 87 (3-7/16) 87 (3.4) 120(4.7)
H
660 (25-49/50) 860 (33-17/20) 830 (32-11/16) 830 (32.7) 1,006(39.6)
I
155 (6-1/10) 155 (6-1/10) 186 (7-5/16) 186 (7.3) 294(11.6)
J
700 (27-11/20) 900 (35-11/25) 298 (11-23/32) 298 (11.7) 380(15)
Capacity(kBtu/h)
Dimension
POSITION OF SUSPENSION BOLT
h Install the unit leaning to a drainage hole side as a figure for easy water drainage.