Submittal Sheet

Table Of Contents
Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
pp
roval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
Performan ce:
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor:
80°FDB/67°FWB
Indoor:
70°FDB/60°FWB
Outdoor:
95°FDB/75°FWB
Outdoor:
47°FDB/43°FWB
Electrical:
PowerSupply(V¹/Hz/Ø)
208230/60/1
MOP(A)
MCA(A)
CoolingRatedAmps(A)
HeatingRatedAmps(A)
Compressor(A)
FanMotor
(
A
)
Piping:
ControlsFeatures :
•Autooperation
•Autorestartopera. on
Defrost/Deicing
Inverter (variable speed
compressor)
Lowambientoperation
to14F (cooling mode)
OperatingRange:
Cooling(°FDB)
Heating(°FWB)
UnitData:
RefrigerantType
R410A
RefrigerantControl
EEV
SoundPressure³(Cool/Heat)±3dB(A)
NetUnitWeight(lbs
)
ShippingWeight(lbs)
He
atExchangerCoating
GoldFin™
MaxNumberofIndoorUnits
Compressor:
Quantity
1
Type
TwinRotary
Oil/Type
FVC68D
Fan:
Type
Propeller
Quantity
FanMotor/Drive
BrushlessDigitallyControlled/Direct
AirflowRate(CFM)
Notes:
RefrigerantCharge(lbs.)
LiquidLine(in,OD)
VaporLine(in,OD)
MaxTotalPiping²(ft)
MaxODUtoIDUPiping
3
(ft)
PipingLength
4
(noadd'lrefrigerant,ft)
MaxElevationbetweenODUandIDU(ft)
MaxElevationbetweenIDUandIDU(ft)
MinNumberofIndoorUnits
2
MOP‐MaximumOvercurrentProtection MCA‐MinimumCircuitAmpacity
ODU‐OutdoorUnit IDU‐IndoorUnit
Page1of3
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com.
Foracompletelistofavailableaccessories,contactyourLGrepresentative.
Cooling(MinRatedMax,Btu/h)
Heating(MinRatedMax,Btu/h)
CoolingPowerInput(MinRatedMax,kW)
HeatingPowerInput(MinRatedMax,kW)
OptionalAccessories:
PI485IntegrationBoard‐PMNFP14A1
ACSmartIV‐PACS4B000
ACP IV - PACP4B000
PowerDistributionIndicator‐
PQNUD1S41
MultiSITE™ CRC1 - PREMTBVC0
MultiSITE CRC1+ - PREMTBVC1
MultiSITE CM - PBACNBTR0A
LonWorks®Gateway‐PLNWKB100
Y-Branch - PMBL5620
AC Smart IV BACnet® Gateway -
PBACNA000
ACPIVBACnetGateway
‐PQNFB17C2
Low Ambient Wind Baffle (Cooling
operation to -4°F) - ZLABGP04A x2
2PortBDUnit‐PMBD3620
3PortBDUnit‐PMBD3630
4PortBDUnit‐PMBD3640
4PortBDUnit‐PMBD3641
1. Acceptableoperatingvoltage:187V253V.
2. Pipinglengthsareequivalent.
3. 180.4ftofMainPiping+49.2ftofBranchPiping.
4. 16ftofMainPiping+131ftofBranchPiping.
5. AtleastoneBDUnitisrequiredforsystemoperaon;amaximumoftwocanbeinstalled
perODUwithuseofYbranchaccessory(PMBL5620).
6. SoundPressurelevelsaretestedinananechoicchamberunderISOStandard1996.
7. Allpower/communicaoncabletobeminimum16AWGfromtheoutdoorunittotheBD
unitand18AWGfromtheBDunittotheindoorunit.
8. Allpower/communicaoncabletobe4conductor,stranded,shieldedandmustcomply
withapplicablelocalandnationalcode.
9. Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcode.
10. SeeEngineeringManualCapacityTablesforODUsensibleandlatentcapacies.
11. SeeEngineeringManualCombinaonTablesforallocaonofODUratedcapacityto each
connectedIDUwhenallarecallingforfullcapacity.Allocationpercentagesshouldbe applied
toODUcapacityatdesignconditions.
12. Thisdataisrated0abovesealevel,with115ofrefrigerantlineanda0level
differencebetweenoutdoorandindoorunits.Allcapacitiesarenetwithacombinationratio
between95105%.
13. MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
14. SeeEngineeringManualCapacityTablesforODUcapacityatdesigncondion.
Restart delay (3-minutes)
Self diagnosis
Soft start
Factory installed Drain Pan
Heater
Required
5
Accessories:
BACnet® is a registered trademark of ASHRAE. LonWorks is a trademark of Echelon
Corporation.
98.4
13,455~41,000~50,200
25.06
54 / 57
SB_MultiF_MAX_LGRED_HP_LMU360HHV_2017_10_19_094903
229.6
12.34
2
0.73 x 2
475.7
45
30.2
49.2
147.6
2,119 x 2
0.96 ~ 2.93 ~ 3.94
25.06
11,700~36,000~46,733
20.4
Ø3/8 x 1
0.72 ~ 2.40 ~ 3.75
14 to +118
249.1
5
222.7
Ø3/4 x 1
-13 to +75