LGRED Heat Installation Manual

61
Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Use a conduit for the communications / connection (power) cable from the outdoor unit to the indoor units and branch distribution unit(s).
Electrical interference my cause product malfunction.
The communications / connection (power) cable from the outdoor unit to the indoor units / branch distribution unit(s) must be separated and
isolated from power wiring to the outdoor unit, computers, radio and television broadcasting facilities, as well as medical imaging equip-
ment. Electrical interference my cause product malfunction.
Multi F with LGRED Systems:
All communication / connection (power) cable from the outdoor unit to the indoor unit
must be a minimum of 18 AWG, four (4) conductor, stranded, shielded or unshielded
(if shielded, it must be grounded to the chassis of the outdoor unit only), and must
comply with applicable local and national codes.
Multi F MAX with LGRED Systems:
All communication / connection (power) cable from the outdoor unit to the branch dis-
tribution unit(s) must be a minimum of 16 AWG, four (4) conductor, stranded, shielded
or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only),
and must comply with applicable local and national codes.
All communication / connection (power) cable from the branch distribution unit(s) to
the indoor units must be a minimum of 18 AWG, four (4) conductor, stranded, shielded
or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only),
and must comply with applicable local and national codes.
Insulation material as required by local code.
5DWHGIRUFRQWLQXRXVH[SRVXUHRIWHPSHUDWXUHVXSWR)
Firmly attach the cable; provide slack but secure in a way to prevent external forces from being imparted on the terminal block.
Wiring must be completed without splices.
&RPPXQLFDWLRQ&RQQHFWLRQ3RZHU&DEOH6SHFLILFDWLRQV
Figure 81: Multi F MAX with LGRED System General Power / Communi-
cations System Schematic.
Power Wiring, Ground,
Communication Cable
From Outdoor Unit
To Indoor Unit or from the
Outdoor Unit to the Branch
Distribution Unit
13/16”
GN/YL
GN/YL = (Ground, Yellow)
7/16" ± 1/8"
Figure 79: Multi F / Multi F MAX Outdoor and
Indoor / Branch Distribution Unit Wiring and Com-
munications Cable Diagram.
Figure 80: Multi F with LGRED System General Power / Communica-
tions System Schematic.
Power Supply
Circuit Breaker
Indoor Unit
Branch Distribution Unit
Ground Wiring
Outdoor Unit
Branch Distribution Unit
Indoor Units
Power Supply
Circuit Breaker
Ground Wiring
Outdoor Unit
ELECTRICAL
&RQQHFWLRQVDQG6SHFL¿FDWLRQV