Forced Cooling Operation Function
Use to add refrigerant to the system when outside ambient temperatures are cool (ex.: winter).
1. Shut power down to the system.
2. Set DIP Switch 1 to ON.
3. Turn power on to the system.
4. Verify that the Red LED on the outdoor unit PCB is ON (indicates indoor units are in forced
cooling operation).
5. Add refrigerant.
• If the green LED light on the outdoor unit PCB is ON, it indicates the compressor is OFF due to
low pressure in the system.
• Turn DIP Switch 1 to OFF after finishing (Normal Operation setting).
• Only the first four DIP switches are functional on the LMU360, 420HHV.