Forced Cooling Operation Function
Use to add refrigerant to the system when outside ambient temperatures are cool (ex.: winter).
1. Shut power down to the system.
2. Set DIP Switch 1 to ON.
3. Turn power on to the system.
4. Verify that the Red LED on the outdoor unit PCB is ON (indicates indoor units are in forced
cooling operation).
5. Add refrigerant.
If the green LED light on the outdoor unit PCB is ON, it indicates the compressor is OFF due to
low pressure in the system.
Turn DIP Switch 1 to OFF after finishing (Normal Operation setting).
Only the first four DIP switches are functional on the LMU360, 420HHV.