Owners Manual

MULTI F OUTDOOR UNIT | 35
Multi F Outdoor Unit Data
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Rated Heating Combination Tables
PERFORMANCE DATA
No. of
Indoor
Units
Indoor Unit Combination
(kBtu/h)
Room Capacity Total Capacity Input (W)
COP HSPF
IDU
1
IDU
2
IDU
3
IDU
4
Total
Unit 1
(Btu/h)
Unit 2
(Btu/h)
Unit 3
(Btu/h)
Unit 4
(Btu/h)
Minimum Rated Maximum
Min. Rated Max.
Btu/h kW Btu/h kW Btu/h kW
Non-Ducted Indoor Units
Three
Units
12 12 18 - 42 10,286 10,286 15,429 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
12 15 15 - 42 10,286 12,857 12,857 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
7 12 24 - 43 5,860 10,047 20,093 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
7 18 18 - 43 5,860 15,070 15,070 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
9 12 24 - 45 7,200 9,600 19,200 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
9 18 18 - 45 7,200 14,400 14,400 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
12 15 18 - 45 9,600 12,000 14,400 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
15 15 15 - 45 12,000 12,000 12,000 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
7 15 24 - 46 5,478 11,739 18,783 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
9 15 24 - 48 6,750 11,250 18,000 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
12 12 24 - 48 9,000 9,000 18,000 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
12 18 18 - 48 9,000 13,500 13,500 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
15 15 18 - 48 11,250 11,250 13,500 - 21,600 6.33 36,000 10.55 41,400 12.13 1,981 2,830 3,962 3.7 9.7
Four
Units
7 7 7 7 28 7,700 7,700 7,700 7,700 18,480 5.42 30,800 9.03 36,960 10.83 1,827 2,610 3,654 3.5 9.0
7 7 7 9 30 7,700 7,700 7,700 9,900 19,800 5.80 33,000 9.67 39,600 11.61 1,883 2,690 3,766 3.6 9.3
7 7 9 9 32 7,700 7,700 9,900 9,900 21,120 6.19 35,200 10.32 41,600 12.19 1,918 2,740 3,836 3.8 9.8
7 7 7 12 33 7,636 7,636 7,636 13,091 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 9 9 34 7,412 9,529 9,529 9,529 21,600 6.33 36,000 10.55 41,600 12.19 1,918
2,740 3,836 3.9 10.0
7 7 9 12 35 7,200 7,200 9,257 12,343 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 7 15 36 7,000 7,000 7,000 15,000 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 9 9 9 36 9,000 9,000 9,000 9,000 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 9 12 37 6,811 8,757 8,757 11,676 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 9 15 38 6,632 6,632 8,526 14,211 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 12 12 38 6,632 6,632 11,368 11,368 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 7 18 39 6,462 6,462 6,462 16,615 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 9 9 12 39 8,308 8,308 8,308 11,077 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 9 15 40 6,300 8,100 8,100 13,500 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 12 12 40 6,300 8,100 10,800 10,800 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 9 18 41 6,146 6,146 7,902 15,805 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 12 15 41 6,146 6,146 10,537 13,171 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 9 9 15 42 7,714 7,714 7,714 12,857 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 9 12 12 42 7,714 7,714 10,286 10,286 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 9 18 43 5,860 7,535 7,535 15,070 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 12 15 43 5,860 7,535 10,047 12,558 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 12 12 12 43 5,860 10,047 10,047 10,047 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 12 18 44 5,727 5,727 9,818 14,727 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 15 15 44 5,727 5,727 12,273 12,273 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 7 24 45 5,600 5,600 5,600 19,200 21,600 6.33 36,000 10.55 41,600 12.19 1,918
2,740 3,836 3.9 10.0
9 9 9 18 45 7,200 7,200 7,200 14,400 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 9 12 15 45 7,200 7,200 9,600 12,000 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 12 12 12 45 7,200 9,600 9,600 9,600 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 12 18 46 5,478 7,043 9,391 14,087 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 9 15 15 46 5,478 7,043 11,739 11,739 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 12 12 15 46 5,478 9,391 9,391 11,739 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 9 24 47 5,362 5,362 6,894 18,383 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
7 7 15 18 47 5,362 5,362 11,489 13,787 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 9 12 18 48 6,750 6,750 9,000 13,500 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
9 9 15 15 48 6,750 6,750 11,250 11,250 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
12 12 12 12 48 9,000 9,000 9,000 9,000 21,600 6.33 36,000 10.55 41,600 12.19 1,918 2,740 3,836 3.9 10.0
Table 28: LMU36CHV with Non-Ducted Indoor Units — Rated Heating Combination Table.
1
Capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
2
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet
bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
3
Wiring cable size must comply with the applicable local and national codes.
4
The specification may be subject to change without prior notice for purpose of improvement.
5