Method 3: Unconditioned Outdoor Air Ducted to Indoor Units
Untreated outdoor air is channeled through a duct system that is piped to the return air duct on Multi F ducted indoor units or to the frame of
Multi F four-way cassettes.
Advantages
• May require less ductwork if indoor units are
placed near outdoor walls or a roof deck.
• Controls must be interlocked to shut off the
outdoor air supply fan when the space is
unoccupied.
• Third-party demand-control ventilation
controls may be installed to regulate outdoor
intake based on the CO
2
levels of the
occupied space.
Disadvantages
• Fan(s) will be required to push outdoor air to the indoor unit to overcome the additional
static pressure.
• Filter required to be added to the outdoor air duct.
• Ducted and four-way cassette models are the only indoor units that accept the connection
of an outdoor air duct to the unit case.
• In most cases, in lieu of using the factory mounted return-air thermistor on indoor units, a
remote wall temperature sensor or zone controller will be needed to provide an accurate
reading of the conditioned area temperature.
• Unconditioned outdoor air may affect indoor unit performance, which may necessitate
oversizing the indoor unit.
2XWVLGHDLUPD\ÀRZEDFNZDUGWKURXJKWKHUHWXUQDLU¿OWHUJULOOHZKHQWKHLQGRRUXQLWIDQVSHHGVORZVRUVWRSVLQUHVSRQVHWRFKDQJHVLQWKH
VSDFHORDG7KLVPD\UHVXOWLQFDSWXUHGSDUWLFXODWHRQWKH¿OWHUPHGLDEHLQJEORZQEDFNLQWRWKHFRQGLWLRQHGVSDFH
OA Wall Cap
Damper
Inline Fan
with Filter
Figure 42: Unconditioned Outdoor Air Ducted to Indoor Units.
BUILDING VENTILATION DESIGN GUIDE
Methodology illustrations are for examples only and do not depict actual
LQGRRUXQLWVIRUWKHVSHFL¿FRXWGRRUXQLWSDLULQJ7KHVHDUHJHQHULFLOOXV-
trations to show ventilation design only.
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
54 | APPLICATION GUIDELINES