Engineering Data Guide

Product Data 47
PTAC
6RWU0-02A YA Chassis
AYH07EALE20(LP076HD2A), AYH07EALE30(LP076HD3A)
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
2.14 1.75 0.40 3.24 1.74 0.42 1.89 1.65 0.53
2.29 1.84 0.51 3.39 1.77 0.52 2.04 1.69 0.60
2.44 1.86 0.55 3.55 1.80 0.55 2.19 1.72 0.63
2.52 1.88 0.55 2.41 1.82 0.55 2.27 1.75 0.63
2.74 1.93 0.55 3.79 1.87 0.56 2.49 1.80 0.65
2.90 1.97 0.65 3.84 1.92 0.57 2.64 1.86 0.66
Outdoor Air Temperature : DB°F
68 77 89.6
Indoor Air
Temperature
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
1.82 1.58 0.56 1.73 1.52 0.42 1.67 1.45 0.53
1.97 1.62 0.62 1.88 1.57 0.52 1.82 1.50 0.54
2.12 1.66 0.65 2.03 1.61 0.55 1.97 1.55 0.55
2.19 1.68 0.65 2.10 1.63 0.55 2.05 1.57 0.55
2.42 1.74 0.68 2.33 1.69 0.56 2.27 1.63 0.56
2.57 1.79 0.69 2.47 1.75 0.57 2.42 1.69 0.57
Outdoor Air Temperature : DB°F
95 104 109.4
Indoor Air
Temperature
AYH09EALE30(LP096HD3A)
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
2.66 2.09 0.60 3.24 2.08 0.62 2.41 1.99 0.73
2.81 2.18 0.71 3.39 2.11 0.72 2.56 2.03 0.80
2.96 2.20 0.75 3.55 2.14 0.75 2.71 2.06 0.83
3.04 2.22 0.75 2.93 2.16 0.75 2.79 2.09 0.83
3.26 2.27 0.75 3.79 2.21 0.76 3.01 2.14 0.85
3.42 2.31 0.85 3.84 2.26 0.77 3.16 2.20 0.86
Outdoor Air Temperature : DB°F
68 77 89.6
Indoor Air
Temperature
WB°F DB°F TC SHC PI TC SHC PI TC SHC PI
57.2 68.0
60.8 71.6
64.4 77.0
66.2 80.6
71.6 86.0
75.2 89.6
2.34 1.92 0.76 2.25 1.86 0.62 2.19 1.79 0.73
2.49 1.96 0.82 2.40 1.91 0.72 2.34 1.84 0.74
2.64 2.00 0.85 2.55 1.95 0.75 2.49 1.89 0.75
2.71 2.02 0.85 2.62 1.97 0.75 2.57 1.91 0.75
2.94 2.08 0.88 2.85 2.03 0.76 2.79 1.97 0.76
3.09 2.13 0.89 2.99 2.09 0.77 2.94 2.03 0.77
Outdoor Air Temperature : DB°F
95 104 109.4
Indoor Air
Temperature
Symbol Notes
DB : Dry Bulb Temperature [°F] 1. All capacities are net, evaporator fan motor heat is deducted.
WB : Wet Bulb Temperature [°F] 2. Indicates nominal maximum capacity.
TC : Total Capacity [kW] 3. Direct interpolation is permissible. Do not extrapolate
SHC : Sensible Heating Capacity [kW]
PI : Power Input [kW]
(Comp.+ indoor fan motor + outdoor fan motor)