Engineering Data Guide
54 Product Data
PTAC
6RWU0-02AControl device
Remote / Local Control
When the Remote/Local dip switch #1 is "ON", it allows the unit to operate by means of Remote Wall Thermostat Control.
When this option is in function, the unit cannot be controlled by means of the knobs.
Energy Saver
When the Energy Saver dip switch #2 is in the "On" position, the indoor fan operates when the compressor is running and
the fan stops operating when the compressor stops running. But when the switch is in the "Off" position, the indoor fan runs
continuously irrespective of the fact that the compressor is running or not.
Front Desk Control
When the paired wire is connected to the two connectors FD2 and FD1(refer to
the figure below), the unit can be turned ON and OFF with a switch located at the
Front Desk Control Panel. When the Front Desk switch is "On", the unit operates
by means of the setting at the Front Desk .And when the Front Desk switch is
"Off", the air conditioning unit operates by the settings made at the Unit itself. In
the "Off" position the Front Desk control cannot be exercised.
Wire # AWG Maximum Length
#22 600ft(180m)
#20 900ft(270m)
#18 1500ft(450m)
#16 2000ft(610m)
(Molex Housing Spec 396-06V)
(recommended wire lengths)
Note: The following figures show
wiring schematics for heat pump
and straight cool units with electric
heat, respectively.
FD2 FD1 DR2 DR1 MS2 MS1
Wiring Schematic for
Remote Heat Pump
Wiring Schematic for
Straight Cool Unit.
Front Desk Control
Front Desk Control
Door Switch
Door Switch
Motion Sensor
Motion Sensor