Standard Efficiency Engineering Manual

84 | APPLICATION GUIDELINES
Single Zone Mega, Standard E󰀩ciency, and Mega 115V Wall Mounted Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Model Numbers
Refrigerant Piping Length (ft.)
16.4 24.6 32.8 41.0 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0
Mega, Standard Efficiency Models
LS090HEV2
(LSN090HEV2 / LSU090HEV2)
Additional
Refrigerant
Charge (oz.)
0 0 1.8 3.6 5.4 - - - - - - -
LS120HEV2
(LSN120HEV2 / LSU120HEV2)
0 0 1.8 3.6 5.4 - - - - - - -
LS180HEV2
(LSN180HEV2 / LSU180HEV2)
0 0 2.1 4.3 6.4 10.7 - - - - - -
LS240HEV2
(LSN240HEV2 / LSU240HEV2)
0 0 2.1 4.3 6.4 10.7 - - - - - -
LS090HFV3
(LSN090HFV3 / LSU090HFV3)
0 0 1.8 3.6 5.4
LS120HFV3
(LSN120HFV3 / LSU120HFV3)
0 0 1.8 3.6 5.4
LS180HFV3
(LSN180HFV3 / LSU180HFV3)
0 0 2.1 4.3 6.4 10.7
LS240HFV3
(LSN240HFV3 / LSU240HFV3)
0 0 2.1 4.3 6.4 10.7
Mega 115V Models
LS090HXV2
(LSN090HXV2 / LSU090HXV2)
Additional
Refrigerant
Charge (oz.)
0 0 1.8 3.6 5.4 - - - - - - -
LS120HXV2
(LSN120HXV2 / LSU120HXV2)
0 0 1.8 3.6 5.4 - - - - - - -
Table 56: Single Zone Mega, Standard Efciency, and Mega 115V Piping System Additional Refrigerant Charge.
Capacity is based on standard length.
Equivalent Pipe Length = Actual Pipe Length + Number of Bends x 0.3.
Additional Refrigerant Charge Calculation : X (g) = [ (Refrigerant Pipe Length) - (No Charge Pipe Length) ] × (Additional Refrigerant).
There is no need to add refrigerant if equivalent pipe is less than the “piping length with no additional refrigerant” in the table above.
REFRIGERANT PIPING DESIGN
Design Guideline Summary