ELECTRICAL DATA
Nominal
Tons
Unit Model
Number
Hertz Voltage
Voltage Range
(Min. to Max.)
MCA MOP
Compressor
Qty.
Compressor Motor
RLA
Outdoor Fan
Motor
Indoor Fan
Motor
Cooling Heating W FLA W FLA
2 LS243HLV3
60 208 - 230 187 - 253
19.0 30 1 14.41 14.41 124 0.4 58 0.5
2-1/2 LS303HLV3 23.0 30 1 15.1 15.1 124 0.25 110 0.5
2-3/4 LS363HLV3 23.0 30 1 15.1 15.1 124 0.25 110 0.5
Table 3: 208-230V, 60Hz, 1-Phase Single-Zone Extended Piping Wall-Mounted Electrical Data.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.