Brochure

57
DUCT-FREE FLOOR STANDING & CEILING CASSETTE SINGLE ZONE
REFRIGERATION QUICK REFERENCE
Floor Standing
Ceiling Cassette
Type
H/P
H/P
H/P
H/P
System #
LF246HV
LF426HV
LC246HV
LC426HV
Indoor Outdoor
230/208 230/208
230/208 230/208
230/208 230/208
230/208 230/208
Voltage
BTUs
24,000
42,000
24,000
42,000

*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
NOTE: Please see local electrical codes for
proper wire specications.
All equipment single phase.
Floor Standing
Ceiling Cassette

Each system is pre-charged with enough refrigerant to charge 25 ft. of line
and the interior unit.
Type
H/P
H/P
H/P
H/P
System #
LF246HV
LF426HV
LC246HV
LC426HV
Pipe size

3/8” 5/8”
3/8” 5/8”
3/8” 5/8”
3/8” 5/8”
BTUs
24,000
42,000
24,000
42,000
Additional
Refrigerant
0.38 oz./ft.
0.43 oz./ft.
0.38 oz./ft.
0.43 oz./ft.
Max. length
each pipe
98’
131’
100’
115’
Max.
elevation
66’
82’
50’
66’
Rated
Amps
11.0/16.1
25.3/24.4
11.0/16.1
25.3/24.4
MCA*
17.6
22.3
17.6
22.3
MOP**
25.0
40.0
25.0
40.0