EXTERNAL STATIC PRESSURE
Table 7: Ceiling-Concealed Ducted (Low Static) Indoor Unit External Static Pressure Setting Values Table.
To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other
than that listed in the table will not provide the desired combination.
Table data is based at 230V. Air flow rate varies according to voltage fluctuation.
Static Pressure (in. wg) 0.1 0.15 0.23 0.31 0.39 0.47 0.55 0.60 0.62 0.70 0.78
Model No. / Nominal Capacity
of System (Btu/h)
Airflow Rate / CFM Setting Value (in. wg)
LHN247HV
24,000
High 688 90 97 108 119 126 134 143 146 149 157 159
Mid 618 86 93 105 115 123 131 140 143 146 153 156
Low 530 82 90 102 112 120 128 137 140 143 150 153
LHN367HV
36,000
High 1,130 - 96 103 109 115 120 126 129 - - -
Mid 953 - 85 96 102 109 115 121 124 - - -
Low 706 - 76 85 95 100 107 113 116 - - -
Indoor Units
Table 8: Ceiling-Concealed Ducted (High Static) Indoor Unit External Static Pressure Setting Values Table.
Static Pressure (in. wg) 0.0 0.04 0.08 0.12 0.16 0.20
Model No. / Nominal Capacity
of System (Btu/h)
Airflow Rate / CFM Setting Value (in. wg)
LDN097HV4
9,000
High 318 98 103 108 116 123 130
Mid 247 82 88 94 102 110 118
Low 194 69 76 83 91 99 109
LDN127HV4
12,000
High 353 95 99 104 109 116 124
Mid 300 86 91 96 101 108 116
Low 247 78 82 87 93 100 108
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
22 | DUCTED
Ceiling-Concealed Ducted System Engineering Manual