Specification Guide
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
46 | DUCTED
Ceiling-Concealed Ducted System Engineering Manual
Altitude Correction Factor
The impact of air density must be considered on systems installed at a significant altitude above sea level, therefore, locally accepted
altitude correction factors must be applied.
Cooling / Heating Correction Factors
For Ceiling-Concealed Ducted systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, deter-
mine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction
factors as shown below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity table using design
conditions. The result is the NET cooling or heating capacity.
Refrigerant Line Length Derates
For air-cooled systems, a capacity correction factor may have to be applied to account for the length of the system’s refrigerant pipe. Rate of
change in capacity due to increased piping lengths is shown below.
Table 27: Low Static Ducted System Cooling and Heating Capacity Coefcient Factors.
Equivalent Piping Length for Piping Components
Piping Length (ft.) 24.6 32.8 49.2 65.6 98.4 131.2 164.0 196.9 229.7 246.0
Cooling Capacity Coefficient Factor
Rate of Capacity
Change (%)
LD097HV4 (9,000) 100 99.7 99.2 98.7 - - - - - -
LD127HV4 (12,000) 100 99.7 99.2 98.7 - - - - - -
Heating Capacity Coefficient Factor
Rate of Capacity
Change (%)
LD097HV4 (9,000) 100 99.7 99.2 98.7 - - - - - -
LD127HV4 (12,000) 100 99.7 99.2 98.7 - - - - - -
Table 28: High Static Ducted System Cooling and Heating Capacity Coefcient Factors.
Component Size (Inches)
Elbow (ft.)
1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/8 1-1/4 1-3/8 1-1/2 1-5/8 1-3/4 2-1/8
0.5 0.6 0.7 0.8 1.2 1.3 1.5 1.6 1.8 2.0 2.1 2.3 2.5 2.8
EQUIPMENT SELECTION PROCEDURE
Table 29: Equivalent Piping Length for Elbows.
Piping Length (ft.) 16.4 32.8 49.2 65.6 98.4 131.2 164.0 196.9 229.7 246.0
Cooling Capacity Coefficient Factor
Rate of Capacity
Change (%)
LH247HV (24,000 Btu/h) 100 99.3 97.9 96.6 93.8 91.1 88.4 - - -
LH367HV (36,000 Btu/h) 100 99.3 97.9 96.6 93.8 91.1 88.4 85.6 82.9 81.5
Heating Capacity Coefficient Factor
Rate of Capacity
Change (%)
LH247HV (24,000 Btu/h) 100 99.7 99.2 98.7 97.7 96.6 95.6 - - -
LH367HV (36,000 Btu/h) 100 99.7 99.2 98.7 97.7 96.6 95.6 94.6 93.5 93.0