Installation Manual

Flaring work
Main cause of gas leakage is defect in
flaring work. Carry out correct flaring work
in the following procedure.
1) Cut the pipes
n Use the accessory piping kit or the
pipes purchased locally.
n Measure the distance between the
indoor and the outdoor unit.
n Cut the pipes a little longer than
measured distance.
n Cut the cable 1.5 m(4.9 ft) longer than
the pipe length.
2) Burrs removal
n Completely remove all burrs from the
cut cross section of pipe/tube.
n Put the end of the copper tube/pipe to
downward direction as you remove
burrs in order to avoid to let chips drop
in the tubing.
3) Putting nut on
n Remove flare nuts attached to indoor
and outdoor units, than put them on
pipe/tube having completed burr
removal.
(Not possible to put them on after
flaring work)
4) Flaring work
n Carry out flaring work using flaring tool
as shown below.
Firmly hold copper tube in a bar(or die)
as indicated dimension in the table
above.
5) Check
n Compare the flared work with figure.
n If flare is noted to be defective, cut off
the flared section and do flaring work
again.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Bar
Copper pipe
"A"
<Wing nut type>
<Clutch type>
16 Vertical Air Handling Unit
Installation
Pipe diameter
Inch (mm)
A Inch (mm)
Thickness
Inch (mm)
Wing nut type
Clutch type
Ø 1/4 (Ø 6.35)
0.04~0.05 (1.1~1.3)
0~0.02
(0~0.5)
0.03 (0.7)
Ø 3/8 (Ø 9.52)
0.06~0.07 (1.5~1.7)
0.03 (0.8)
Ø 1/2 (Ø 12.7)
0.06~0.07 (1.6~1.8)
0.03 (0.8)
Ø 5/8 (Ø 15.88)
0.06~0.07 (1.6~1.8)
0.04 (1.0)
Ø 3/4 (Ø 19.05)
0.07~0.08 (1.9~2.1)
0.04 (1.0)