Accessories Brochure

24
Indoor Model Number LAN090HSV4 LAN120HSV4 LAN180HSV4
Capacity
1
(BTU/hr) 9,000 BTU Class 12,000 BTU Class 18,000 BTU Class
Controller Wireless LCD Remote Wireless LCD Remote Wireless LCD Remote
Controller operating range
Cooling
18 ~ 30°C (64 ~ 86°F) 18 ~ 30°C (64 ~ 86°F) 18 ~ 30°C (64 ~ 86°F)
Heating
16 ~ 30°C (61 ~ 86°F) 16 ~ 30°C (61 ~ 86°F) 16 ~ 30°C (61 ~ 86°F)
WLAN Smart Phone Control No No No
Dimension W x H x D (Inch) 35 1/4 x 11 3/8 x 8 1/16 35 1/4 x 11 3/8 x 8 1/16 40 9/16 x 12 25/32 x 9 21/32
Net Weight (Lbs) 23.1 23.1 32
Power Supply (Ø / V /Hz) 1 / 208~230 / 60 1 / 208~230 / 60 1 / 208~230 / 60
Running Current .2A .2A .3A
Connecting Wire Outdoor To Indoor
2
: (LMU18CHV, LMU24CHV,
LMU30CHV, MU36CHV, LMU187HV, LMU247HV, LMU369HV)
4 x minimum 16# (ground included)
stranded, rated at 300V minimum
4 x minimum 16# (ground included)
stranded, rated at 300V minimum
4 x minimum 16# (ground included)
stranded, rated at 300V minimum
Connecting Wire Distributor Box To Indoor²
2
:
(LMU480HV & LMU540HV + PMBD36xx)
4 x minimum 18# (ground included)
stranded, rated at 300V minimum
4 x minimum 18# (ground included)
stranded, rated at 300V minimum
4 x minimum 18# (ground included)
stranded, rated at 300V minimum
Air Flow Rate (cfm) Max ~ Hi ~ Med ~ Low 423 ~ 353 ~ 272 ~ 191 423 ~ 353 ~ 272 ~ 191 735 ~ 622 ~ 509 ~ 399
Sound Pressure (dBA) Hi ~ Med ~ Low ~ Sleep 8 ~ 33 ~ 23 ~ 19 8 ~ 33 ~ 23 ~ 19 45 ~ 40 ~ 35 ~ 29
Condensate Switch Connection Yes Yes Yes
Condensate hose connection OD (Inch) 5/8 5/8 5/8
Liquid Line Connection (Inch) 1/4 1/4 1/4
Gas Line Connection (Inch) 3/8 3/8 1/2
Charge Adjustment Over Precharge Length (Oz / Ft) .22 .22 .22
Warranty: 5 years parts
9,000 - 18,000 BTU (LAN090HSV4, LAN120HSV4 & LAN180HSV4 Universal Indoor Units)
Multi F Art Cool™ Mirror
LMAN
LAN180HSV4 will use a 1/4 & 1/2 lineset with any Multi F outdoor unit.
LAN180HSV4 will use a 3/8 & 5/8 lineset with LSU180HSV4.
Optional Accessories:
• PREMTB10U programmable wired controller
• PZCWRG3 Group Control / Extension Wire
• PDRYCB300 Third Party Thermostat Adapter Kit
• PRARS0 Auxiliary Heat Relay (requires PREMTB10U wired controller)
1
Refer to the Engineering Manual for capacity charts at http://LGcomfort.ca/en/engineering-resources.aspx
2
All electrical wiring must comply with applicable local, provincial and national codes.