ENGLISH FRANÇAIS ITALIANO DEUTSCH OWNER’S & INSTALLATION MANUAL ESPAÑOL NEW STANDARD REMOTE CONTROLLER РУССКИЙ ЯЗЫК POLSKI PORTUGUÊS Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly..
TIPS FOR SAVING ENERGY 2 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below: READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE. • • • • • • Do not cool excessively indoors. This may consume more electricity. Block sunlight with blinds or curtains while you are operating the air conditioner.
4 IMPORTANT SAFETY INSTRUCTIONS • Do not clean using powerful detergents like solvent but use soft cloths. There is risk of fire, electric shock, explosion, equipment malfunction or deformation. • Do not press the screen using powerful pressure. There is risk of product break-down or malfunction.
6 TABLE OF CONTENTS 49 50 51 52 53 Timer entrance and setting method Simple timer Sleep timer Turn-off Reservation Turn-on Reservation 54 SCHEDULE SETTING 54 55 56 57 58 How to enter schedule Daily Schedule Schedules & Edit Schedules & Edit – Add schedule Exception day 59 ENERGY (air conditioner / DX ventilator) 59 60 61 63 64 65 66 67 68 69 70 How to enter energy Instantaneous power check Energy consumption Energy saving - Temperature Setback Timer Energy saving - Time Limit Control Energy setting
8 DESCRIPTION READ BEFORE OPERATING THE CONTROLLER READ BEFORE OPERATING THE CONTROLLER Menu Structure NEW STANDARD REMOTE CONTROLLER Menu Override ......................................................................................................................35 Fine Dust ......................................................................................................................36 Sub function Energy Saving Operation display window Back button ....................................
10 READ BEFORE OPERATING THE CONTROLLER READ BEFORE OPERATING THE CONTROLLER ...............................80 ...............................81 Home Leave Set Temp ...............................82 Energy Consumption Comfort Cooling ...............................83 Year-on-year Usage ..........................61 Weekly Usage ..........................61 Monthly Usage ..........................61 Defrost Mode ...............................84 Yearly Usage ..........................
12 READ BEFORE OPERATING THE CONTROLLER READ BEFORE OPERATING THE CONTROLLER 13 Service Contact ..........................110 Model Information ..........................111 RMC Version Information ..........................112 Error History ..........................113 Open Source License ..........................114 IDU Auto-Start .............................146 Occupancy Duration Time .............................147 CN_CC .............................148 CN_EXT ....................
14 DESCRIPTION OF THE OPERATION DESCRIPTION OF THE OPERATION 15 Setting screen Select the category to set using [∧,∨(up/down)] button. Main screen In each detail screen of the menu, as in the box in the left figure, when “<,>” icons are displayed at the same time, you can immediately apply the setting value by pressing [<, >(left/right)] button. ※ For the values that can be set in each category, refer to the detail manual for each function.
16 DESCRIPTION OF THE OPERATION DESCRIPTION OF THE OPERATION Interface screen In the main screen, you can enter the monitoring / sub function screen by pressing [Back] button and then pressing [<, >(left/right)] button. - In the monitoring screen, you can check the indoor temperature and outdoor unit monitoring information. - In the sub function screen, you can turn on or off the sub function supported by the product.
18 OPERATION SETTING OPERATION SETTING 19 Cooling Operation On / Off Cooling operation’s minimum setting temperature is 18°C (16°C). For some types of the indoor units, the desired temperature can be controlled in the units of 1°C or 0.5°C. Air conditioner and ventilator will be turned on or off. Press the remote controller’s (On/Off) button. - If the product is in operation, On/Off button will be illuminated. If the product is in off, On/Off button backlight will be off.
20 OPERATION SETTING OPERATION SETTING 21 Dry Operation The heating operation’s minimum setting temperature is 16°C. For some types of the indoor units, the desired temperature can be controlled in the units of 1°C or 0.5°C. Dry operation’s initial fan speed is “Low”. Dry operation does not have a separate desired temperature. - Set the desired temperature higher than the indoor temperature. - Indoor temperature is displayed on the default screen of the remote controller.
22 OPERATION SETTING OPERATION SETTING 23 AI / Auto operation Fan only operation’s initial wind strength is “High”. Fan only operation does not have a separate desired temperature. Auto operation’s initial desired temperature is 25°C. The cooling exclusive model’s initial desired temperature is “It’s Fine”. Cooling/heating model’s desired temperature can be controlled in the units of 1°C or 0.5°C. For cooling exclusive model, the value can be controlled from “hot” stage to “cold” stage.
24 OPERATION SETTING OPERATION SETTING 25 Power Cool Operation The indoor unit automatically manages room temperature with extended heating and cooling setting temperature ranges. Dual setpoint auto mode can be set in the USER SETTING. This is recommended in North America region. Power cooling quickly lowers the indoor temperature.
26 OPERATION SETTING - VENTILATOR TEMPERATURE SETTING 27 ENGLISH OPERATION SETTING - VENTILATOR TEMPERATURE SETTING Operation mode Controlling Desired Temperature Ventilation (general and direct cooling type ventilation) operation mode supports the following operation modes. ※Some products may not support some operation modes. You can easily control to the desired temperature.
28 TEMPERATURE SETTING WIND SETTING 29 WIND SETTING You can check the current indoor temperature. • In the remote controller’s the main screen, you can check the indoor temperature. Fan speed control From the main screen, press [<,>(left/right)] button to select the fan speed category, and press [∧,∨(up/down)] button to set the fan speed control the desired fan speed. - It circulates in the order of Slow ↔ Low ↔ Medium ↔ High ↔ Power ↔ Auto. ※For some product some fan speed may not be available.
30 HOME LEAVE SETTING HOLD SETTING 31 HOLD SETTING Home leave (Unoccupied Mode) Hold The "Home Leave" function enables proper operation of indoor unit when a space is left for a period of time. This feature can only be used when Control type setting is set to the Dual Set Point Control mode User can use this function when they want to manage indoor unit as home leave control mode only.
32 ADDITIONAL OPERATION –VENTILATION EXTERNAL EQUIPMENT CONTROL SETTING 33 EXTERNAL EQUIPMENT CONTROL SETTING Additional operation External equipment control You can change the additional operation of the ventilation product. • In the main screen, press [<,>(left/right)] button to select the additional operation category, and press [∧,∨(up/down)] button to set the additional operation. It is the function to set the contact point output of the external equipment control mode.
34 PLASMA PURIFICATION SETTING OVERRIDE CONTROL SETTING 35 OVERRIDE CONTROL SETTING Plasma Purification Override control It cleans and makes pleasant indoor air. 1. Plasma Purification - single operation If plasma purification is turned on in operation Off state, plasma purification single operation is performed. In dual setpoint setting, wired remote controller can manages indoor unit status based on programmed control events which have occupancy option.
36 MONITORING SCREEN How to enter fine dust status screen • In the main screen, press [Back] button to move to monitoring/additional functions screen, and press [<, > (left/right)] button to move to fine dust status screen. (Method 1) Fine dusts status It is the function to monitor dust value measured by the dust sensor mounted inside the air conditioner. • In the fine dust status screen, you can check fine dust, ultra fine dust, and super ultra fine dust concentration values.
38 ADDITIONAL FUNCTION SETTING ADDITIONAL FUNCTION SETTING 39 Energy Saving Setting Sub function entrance and setting method The energy saving cooling function is the function to control the desired temperature during the cooling operation to improve the comfort of the user and to improve the power saving performance. In the menu screen, press [<,>(left/right)] button to select the sub function category, and press [OK] button to move to the sub function setting list screen.
40 ADDITIONAL FUNCTION SETTING ADDITIONAL FUNCTION SETTING 41 Fan Auto Setting It makes the indoor air clean and pleasant. Select fan operation after performing thermal control of indoor units. If set to 'ON', fan operation keeps on after thermal operation of indoor units. ! NOTE The air cleaning function is an additional function, and it may not be displayed/operated in some products. The air cleaning function is possible only when the product is in operation.
42 ADDITIONAL FUNCTION SETTING ADDITIONAL FUNCTION SETTING 43 Electric Heater Setting It is the function to activate the humidifier installed in the product when the indoor air is dry. It is the function to reinforce the heating capability by turning on the electric heater during the heating operation. ! NOTE The humidification function is an additional function, and it may not be displayed/operated in some products. ! NOTE It can be set only in the heating operation.
44 ADDITIONAL FUNCTION SETTING ADDITIONAL FUNCTION SETTING 45 Ventilation kit Setting Robot cleaning function is the function to automatically perform the filter cleaning with the cleaner in the product when the air conditioner is used for certain period of time. Function enables operation of an optional ventilation kit with indoor units ! NOTE It can be set 30 seconds after the operation stopped.
46 ADDITIONAL FUNCTION SETTING ZONE CONTROL SETTING 47 ZONE CONTROL SETTING The comfort cooling is the function to automatically control the cooling strength to maintain the pleasant feeling without turning off the product after the indoor temperature reached the desired temperature. Zone Control A function to control zone with duct type indoor units. Wired Remote controller can control maximum 8 zones.
48 LOCK SETTING TIMER SETTING 49 ENGLISH LOCK SETTING TIMER SETTING How to enter lock setting Timer entrance and setting method • In the menu screen, press [<,>(left/right)] button to select “lock setting” category, and press [OK] button to move to the lock setting list screen. • In the lock setting list, if you press [∧ ,∨(up/down)] button, you can turn on/off the corresponding lock function.
50 TIMER SETTING TIMER SETTING 51 Sleep timer You can easily set the timer in the range of 1~7 hours in the units of 1 hour. Sleep timer is the function to operate the air conditioner in sleep mode before going to sleep for certain hours and stop the operation. OK ! NOTE If the product operation is On, the easy timer turns off the operation after the corresponding time. If the product operation is Off, the easy timer turns on the operation after the corresponding time.
52 TIMER SETTING LOCK SETTING 53 Turn-on Reservation The product is automatically turned Off at the set timer time. The product is automatically turned On at the set timer time. OK ! NOTE Even if the Turn-off Reservation operation is turned On/Off after the setting and before the timer operation, the set timer is not cleared. OK ! NOTE Even if the Turn-on Reseravation operation is turned On/Off after the setting and before the timer operation, the set timer is not cleared.
54 SCHEDULE SETTING SCHEDULE SETTING 55 Daily Schedule How to enter schedule It is the function that can check the status of the timer (schedule) saved in the remote controller. • In the schedule list, select the daily schedule status category, and press [OK] button to move to the detail daily schedule status screen. • In the menu screen, press [<,>(left/right)] button so select the schedule category, and press [OK] button to move to the schedule setting list screen.
56 SCHEDULE SETTING SCHEDULE SETTING 57 Schedules & Edit – Add schedule It is the function that can check the status of the timer (schedule) saved in the remote controller. Description of each stage in Add schedule ENGLISH Schedules & Edit • In the schedule list, select the daily schedule status category, and press [OK] button to move to the daily schedule status detail screen. • You can use the remote controller’s [<,>(left/right)] button to check other date’s timer information.
58 SCHEDULE SETTING It is the function to automatically stop the operation on the set timer day. • In the schedule list, select the exception day category, and press [OK] button to move to the Exception day designation detail screen. • In the exception day, you can check, and add/change/delete the exception day information saved in the remote controller. - To add an exception day, in the Exception day registration detail screen, designate year/month/day, and press [OK] button to save the Exception day.
60 ENERGY ENERGY 61 Energy consumption It is the function that can check the product’s instantaneous power. ※There may be some error with the actual instantaneous power, so use it only for reference. • In the energy list, select the “Instantaneous power” category, and press [OK] button to move to the detail screen. You can check the energy consumption (operation time, power consumption). ※There may be some error with the actual consumption, so use it only for reference.
62 ENERGY ENERGY 63 List Description Power consumption Operation time You can see the power consumption compared to the same month of the previous year. You can see the operation time compared to the same month of the previous year. Weekly usage It displays the daily power consumption of the current month. It displays the daily operation time of the current month. Monthly usage It displays the weekly power consumption of the current month.
64 ENERGY ENERGY 65 Energy setting - outdoor unit capacity setting It is the function to stop the product operation after the set time after starting the product operation for the energy saving. • In the energy saving list, select “time limit control” category, and press [OK] button to move to the time limit control setting screen. It is the function that can set the outdoor unit capacity. • In the energy list, select “energy setting” category, and press [OK] button to move to the energy setting screen.
66 ENERGY ENERGY 67 Energy setting - target power consumption It is the function that can set the Instantaneous power’s target value. You can set the target value to find the power consumption status. • In the energy setting list, select “target Instantaneous power” category, and press [OK] button to move to the target Instantaneous power setting screen. It is the function to set the target power consumption per hour.
68 ENERGY ENERGY 69 Energy setting - Alarm Popup Setting It is the function that can set the Instantaneous power’s target value. You can find the power consumption status by setting the target value. • In the energy setting list, select “target operation time” category, and press [OK] button to move to the target operation time setting screen. It is the function to set whether to use the target power consumption and the target operation time notice popup window.
70 ENERGY FUNCTION SETTING FUNCTION SETTING It is the function to initialize all of the power consumption and operation time information. • In the energy setting list, select “consumption data initialization” category, and press [OK] button to move to the consumption data initialization setting screen. How to enter function setting OK ENGLISH Energy setting – Usage data initialization To enter the menu displayed at the bottom, you need to enter the function setting menu as follows.
72 FUNCTION SETTING FUNCTION SETTING 73 Menu Vane angle control setting Description Vane up/down control setting You can control the Air Direction angle. Elevation grill setting It is the function to operate the Elevation grill for the indoor unit filter cleaning. Robot cleaning setting Robot cleaning function is the function to automatically perform the filter cleaning with the cleaner of the product when the air conditioner is used for certain time period.
74 FUNCTION SETTING FUNCTION SETTING 75 Robot cleaning setting It is the function to operate the Elevation grill for the indoor unit filter cleaning. - While the product operation is stopped, if you use [<,>(left/right)] button to select the setting value, the grill operation status changes. Robot cleaning function is the function to perform the automatic filter cleaning with the cleaner of the product when the conditioner is used for certain period of time.
76 FUNCTION SETTING FUNCTION SETTING 77 Change temperature setting Change Temperature is the function to set the automatic Change Temperature between cooling and heating operation according to the temperature in AI operation mode. • In the function setting list, select the Change Temperature category, and press [OK] button to move to the detail screen. OK OK Value 1~7°C(Default : 2°C) It is the function that can be used only in cooling/heating product.
78 FUNCTION SETTING FUNCTION SETTING 79 Wi-Fi pairing setting Dead Band function is used with a dual setpoint mode. When heating and cooling desired temperatures have been changed, the set value will maintain a difference between the heating and cooling desired temperature. • In the function setting list, select the dead band category, and press [OK] button to move to the detail screen. It is the function to perform the pairing function of the Wi-Fi module connected to the indoor unit.
80 FUNCTION SETTING FUNCTION SETTING 81 Override Set Time Setting Zone name settings allow you to select zone name. Override Set Time function can only be used in Dual Setpoint Control mode. When timed override is used, the set time will be a default value. OK OK OK ! NOTE Override Set Time function can only be used in a dual setpoint control mode. ! NOTE Zone name setting function may not work in some indoor unit products.
82 FUNCTION SETTING FUNCTION SETTING 83 Comfort cooling setting (air conditioner / DX ventilator) Home Leave Set Temperature function is used in Dual Setpoint Control mode. When customer operate as home leave mode, this setting temperature value will be applied. It is the function to set the outdoor unit Comfort saving operation value. • You can set the following values using [<,>(left/right)] button.
84 FUNCTION SETTING FUNCTION SETTING 85 Smart load control(SLC) setting (air conditioner / DX ventilator) Change the outdoor unit’s defrost mode operation. • Select value using [<,>(left/right)] button. Change the outdoor unit’s Smart Load Control stage value. (Smart load control is the function to calculate the indoor air temperature, outdoor air temperature, and humidity to operate effectivly.
86 FUNCTION SETTING FUNCTION SETTING 87 Advanced fan speed “Auto” setting It is the function to set the start and end time of the outdoor unit’s low noise mode operation. • In the function setting list, select the Low Noise Mode Time category, and press [OK] button to move to the detail screen. - After setting the start time and the end time, press [OK] button to move to the upper level list.
88 FUNCTION SETTING FUNCTION SETTING 89 Midnight air cooling (ventilation interface) It is the function to set the ventilation operation to start after the delay time. • In the function setting list, select the delay time category, and press [OK] button to move to the detail screen. - After setting the minute, press [OK] button to move to the upper level list. It is the function to discharge indoor air and supply cool outdoor air into the indoor during summer nights to save energy.
90 FUNCTION SETTING FUNCTION SETTING 91 ENGLISH Human detection mode setting It is the function that enables energy saving through the human detection power saving operation and wind direction setting. In the function setting list, select human detection operation mode category and press [OK] button to move to the lower level setting list. After selecting human detection wind direction category, you can set the following setting values using [<,> (left/right)] button.
92 USER SETTING USER SETTING 93 How to enter user setting To enter the menu displayed at the bottom, you need to enter the user setting menu as follows. • Select the setting category, and press [OK] button to move to the setting list. • Select the user setting category, and press [OK] button to move to the user setting list. Set the language to be displayed on the remote controller. • In the user setting list, select the language category, and press [OK] button to move to the detail screen.
94 USER SETTING USER SETTING 95 Temperature unit setting It is the function to set GUI type on the remote controller. * Dual setpoint type is a function that makes it possible to set the cooling and heating target temperature simultaneously. It is recommended for customers accustomed to using North American thermostats. We recommend that you use it only in the region (North America).
96 USER SETTING USER SETTING 97 LCD brightness in idle setting Adjust the screen Off time of the remote controller. • Select the following setting values using [<,>(left/right)] button. Adjust the remote controller’s screen brightness. • Select the following setting values using [<,>(left/right)] button. Value 15sec 30sec (default) ! CAUTION Selecting longer stand by screen will decrease LCD lifespan.
98 USER SETTING USER SETTING 99 External device types Set the name of external equipment and equipment logic setting • In the user setting list, select the external device setting category, and press [OK] button to move to the detail screen. It is the function to set the name of the External device attached to the remote controller. • You can set the following setting values using [<,>(left/right)] button.
100 USER SETTING USER SETTING 101 Date setting It is the function to set to use the information managed by the wired remote controller as the contact point control condition to widen the usage of the contact point (Digital Output) installed in the remote controller. Set the date displayed on the remote controller. • In the user setting list, select the date category, and press [OK] button to move to the detail screen.
102 USER SETTING USER SETTING 103 Summer time setting Set the time displayed on the remote controller. • In the user setting list, select the time category, and press [OK] button to move to the detail screen. • After the setting, if you press [OK] button, the setting is saved and moves to the previous screen. Set the daylight savings time dates in the remote controller. • In the user setting list, select the summer time setting category, and press [OK] button to move to the detail screen.
104 USER SETTING USER SETTING 105 Schedule initialization Set the password to prevent unauthorized change to remote controller settings. • Select the user password setting category, and press [OK] button to move to the detail screen. - If the password is set, when you enter “menu – setting”, you need to input password to enter the setting list. - When you forgot the password, you can initialize the password using the installer setting’s “password initialization”. The initialized password is “0000”.
106 USER SETTING USER SETTING 107 Humidity display Set the theme of the remote controller screen. • Select either white or black using [<,>(left/right)] button. It is the function to decide whether to display humidity on the main screen and additional information screen. You can use [<, > (left/right)] button to set the setting values (On or Off). ON Display humidity. OFF Do not display humidity.
108 USER SETTING SERVICE SETTING 109 ENGLISH System restart SERVICE SETTING Restart the remote controller. • In the user setting list, select the system restart setting category, and press [OK] button to move to the detail screen. - In the detail screen, when you press [OK] button, a popup message is displayed, press the check button, to restart the system. - For forced reset, press down [On/Off + Back] button for 5 seconds to restart the system.
110 SERVICE SETTING SERVICE SETTING 111 Model information (air conditioner / DX ventilator) Check and input the service center phone number that you can call when there is service issue. • In the service setting list, select the service contact point and press [OK] button to move to the detail screen. • While “edit” button is selected, press [OK] button to move to the edit screen, change it, and press [OK] button to change the service contact point.
112 SERVICE SETTING SERVICE SETTING 113 Error history Check the indoor/outdoor product group and capacity information to which the remote controller is connected. • In the service setting list, select the remote controller version information check category, and press [OK] button to move to the detail screen. View the connected indoor unit’s error history. • In the service setting list, select ‘check error history’ category, and press [OK] button to move to the detail screen.
114 SERVICE SETTING INSTALLATION 115 ENGLISH Open source license INSTALLATION View the remote controller’s open source license. • In the service setting list, select the open source license category, and press [OK] button to move to the detail screen. Installation of Remote Controller • After fixing the remote controller installation plate on the desired location, fix it firmly with the provided screws.
116 INSTALLATION INSTALLATION 117 ENGLISH • When you remove the remote controller from the installation plate, insert a small flat head screwdriver into the bottom side separation hole and turn clockwise to separate the remote controller. - There are 2 separation holes at the bottom part. Slowly separate one by one. - Be careful not to damage the internal parts during the removal. Group control • It connects and controls 2 or more air conditioner indoor units to one wired remote controller.
118 INSTALLATION - After completing the master/slave setting in the indoor unit product, turn Off the power of the indoor unit product, and turn On the power after 1 minute. ! NOTE • During the group control, set only 1 indoor unit as master. • During the group control, some functions other than the basic operation setting, fan speed Low/Med/High, remote controller lock setting, and time setting may be limited.
120 AIR CONDITIONER AND VENTILATION INTERFACE INSTALLER SETTING 121 • It controls using the wired remote controller at a place where the air conditioner indoor unit and the ventilation product are connected and installed at the same time. - When the power is applied, the remote controller recognizes the product and operates normally.
122 INSTALLER SETTING INSTALLER SETTING 123 • You can set the product user functions. • Some functions may not be displayed/operated in some product types. Menu Description Test run setting It is the function to set the trial operation at the initial product installation. Central control address Setting It is the function to set the central control address of the indoor unit during the central controller connection.
124 INSTALLER SETTING INSTALLER SETTING 125 Test run setting (air conditioner / DX ventilator) • You can set the product user functions. • Some functions may not be displayed/operated in some product types. After product installation, the Test run must be performed. For Test run related details, refer to the product manual. • In the installer setting list, select the Test run setting category, and press [OK] button to move to the detail screen.
126 INSTALLER SETTING INSTALLER SETTING 127 ESP setting (air conditioner / general, DX ventilator) It is the function to set the central control address of the indoor unit to allow communication with a central controller, • In the installer setting list, select the central control address setting category, and press [OK] button to move to the detail screen. - Select a hex value between 00 and FF.
128 INSTALLER SETTING INSTALLER SETTING 129 Ceiling height setting (air conditioner) It is the function to control the fan speed stage according to the ceiling height in the ceiling type product. • You can set the following setting values using [<,>(left/right)] button.
130 INSTALLER SETTING INSTALLER SETTING 131 Static pressure setting can be set only in the duct products. (It cannot be set in other products.) • You can set the following setting values using [<,>(left/right)] button. Remote controller master / slave setting (air conditioner / General, DX ventilator) This function sets configuration for the master/slave setting through the remote controller. • Change setting values using [<,>(left/right)] button.
132 INSTALLER SETTING INSTALLER SETTING 133 The operation master / slave selection function is to avoid other mode operations, and it is the function to prevent the selection of opposite mode of the indoor unit master by the indoor units set as slaves. • Change setting values using [<,>(left/right)] button. Dry contact mode setting (air conditioner / DX ventilator) Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.
134 INSTALLER SETTING INSTALLER SETTING 135 Zone Type Setting(air conditioner) It is the function to apply different fan speeds automatically for each thermal control status. • You can set the following setting values using [<,>(left/right)] button. This function is only available on some products. This function select a type of zone control type which indoor unit support as 'new type' or 'old type'.
136 INSTALLER SETTING INSTALLER SETTING 137 Function control during group Control setting (air conditioner) Enable the emergency heater control function and the usage environment. • In the installer setting list, select the emergency heater setting category, and press [OK] button to move to the detail screen.
138 INSTALLER SETTING INSTALLER SETTING 139 Expand of Temperature Range (air conditioner) At the Code field, select when air cleaner/heater/humidifier/elevation grill/ventilation KIT/Aux Heater/refrigerant leakage detection sensor are newly installed to the indoor unit or when an installed KIT is removed. • You can set the following setting values using [<,>(left/right)] button. This function using in dual setpoint control mode. This function is used for select setting temperature range option.
140 INSTALLER SETTING 141 Static pressure step setting (air conditioner) This function allows you to check the address of the indoor unit designated by the outdoor unit. • In the installer setting list, select the indoor unit address check category, and press [OK] button to move to the detail screen. It is the function to subdivide and set the product’s Static pressure to 11 stages. • Change setting values using [<,>(left/right)] button.
142 INSTALLER SETTING INSTALLER SETTING 143 Fan speed in Cooling thermal off (air conditioner) It is a function that sets the minimum running time of outdoor unit cycle mode when switching from cooling mode to heating mode and vice versa during Auto Operation mode. Under the condition of cooling/heating switching, it switches between cooling and heating mode after operation during the time scheduled in the Guard timer. Indoor unit fan, in cooling mode, during thermal off condition.
144 INSTALLER SETTING INSTALLER SETTING 145 It is the function to set the air conditioner fan operation if the ventilation is operated while the air conditioner operation is stopped when the air conditioner and the ventilation are installed to interface with each other. • You can set the following setting values using [<,>(left/right)] button.
146 INSTALLER SETTING INSTALLER SETTING 147 Occupancy duration time setting(air conditioner) It is a function that sets whether to restore the indoor unit operation by resuming the previous power-on state or as power-off state in the power failure compensation. • You can set the following setting values using [<,>(left/right)] button. It is a function that sets the light-on/occupancy duration after motion is detected when installing an occupancy sensor.
148 INSTALLER SETTING INSTALLER SETTING 149 CN_EXT setting (air conditioner / DX ventilator) It is the function to set the usage of the indoor unit’s CN_CC port. • Select CN_CC setting category, and press [OK] button to move to the detail screen. It is the function to set to control the external input and output according to DI/DO set by the customer using the indoor unit’s Dry Contact Port. (It is the function to decide the usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.
150 INSTALLER SETTING INSTALLER SETTING 151 It is the function to set the outdoor unit’s function Master / Slave. • You can set the following setting values using [<,>(left/right)] button.
152 INSTALLER SETTING INSTALLER SETTING 153 Human detection sensor It is the function to set the low noise mode control main agent. (It is the function to set that only one of the outdoor unit / remote controller can control the low noise operation.) • You can set the following setting values using [<,>(left/right)] button. It is the function to set whether to install human detection sensor and operation standard value.
154 INSTALLER SETTING INSTALLER SETTING 155 ODU cycle priority (airconditioner) It is the function to set the location to detect humidity. You can use [<, > (left/right)] button to set the following setting values. This function can set cycle priority of outdoor unit. Multi V Heat Pump system does not support mixed mode therefore wired remote controller can not show opposite operation mode for select option while ODU operate cooling or heating cycle.
156 INSTALLER SETTING INSTALLER SETTING 157 Description Not use Does not support opposite cycle operation using wired remote controller - When ODU operate as cooling cycle selectable operation modes with wired remote controller are cool, auto, dehumidification and fan. - When ODU operate as heating cycle selectable operation modes with wired remote controller are heat, auto and fan Standby When user set opposite operation mode using wired remote controller indoor unit stop thermal operation and fan.
158 INSTALLER SETTING INSTALLER SETTING 159 Password initialization (air conditioner / general, DX ventilator) This function can set to display energy data which outdoor unit estimated power consumption data without wattmeter. It is the function to initialize (0000) when you forgot the password set in the remote controller. • In the installer setting list, select the password initialization setting category, and press [OK] button to move to the detail screen.
160 INSTALLER SETTING INSTALLER SETTING 161 Express ventilation priority (general , DX ventilator) It is the function to set the direction of the ventilation product. • Select value using [<,>(left/right)] button. It is the function to set the priority of the air supply and air discharge during the express ventilation operation. • Select value using [<,>(left/right)] button.
162 INSTALLER SETTING INSTALLER SETTING 163 Humidification of ventilation with heating operation (DX ventilator) It is the function to set whether to use the humidification function during the ventilation product single operation. • Select value using [<,>(left/right)] button. It is the function to set the heating humidification function of the direct ventilation to be automatic or manual. • Select value using [<,>(left/right)] button.
164 INSTALLER SETTING GUIDE TO DIFFERENT MODE OPERATION/OPEN SOURCE SOFTWARE 165 It is the function to change the standard fan speed of the ventilation product. • Select value using [<,>(left/right)] button. GUIDE TO DIFFERENT MODE OPERATION/OPEN SOURCE SOFTWARE Different mode operation Different mode operation is the case when the indoor units’ operation modes are different when multiple indoor units are installed to one outdoor unit.