Owner's Manual

139
INSTALLER SETTING
138
INSTALLER SETTING
ENGLISH
External devices of indoor unit setting (air conditioner)
At the Code field, select when air cleaner/heater/humidifier/elevation grill/ventilation KIT/Aux
Heater/refrigerant leakage detection sensor are newly installed to the indoor unit or when an in-
stalled KIT is removed.
• You can set the following setting values using [<,>(left/right)] button.
Function Value
Plasma purification
Not install / Install
Heater
Humidifier
Elevation grill
Ventilation Kit
Aux Heater
Refrigerant leakage detection sensor
Expand of Temperature Range (air conditioner)
This function using in dual setpoint control mode.
This function is used for select setting temperature range option.
NOTE
!
When the set values are changed, the items below will be initialized.
- Target temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
'home leave' temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
In case of the setting expanded temperature range (set), please note that the setting of the
wired remote controller can be altered under below circumstances.
- In case of cooling at 30~37.5 °C(64~99 °F), it is changed to cooling at 86 °F(30 °C).
- In case of heating at 4~15.5 °C(40~86 °F), it is changed to heating at 60 °F(16 °C).
- If set on dual setpoint, it is changed to the current operation mode(cooling or heating) of
the indoor unit.
Situation where changes in the setting occur
a. Operates the Auto address work and pipe search in situations such as product installment
and service.
b. Occurrence of errors and deactivation.
c. Command generated by the central control, outdoor unit, Dry contact, Remote controller,
indoor unit switch.
Value
Clear : 60~86 °F / 16~30 °C (default)
Set : 40~99 °F / 4~37.5 °C