Owner's Manual

153
INSTALLER SETTING
152
INSTALLER SETTING
ENGLISH
Low Noise Mode Priority setting (air conditioner / DX ventilator)
It is the function to set the low noise mode control main agent. (It is the function to set that only
one of the outdoor unit / remote controller can control the low noise operation.)
• You can set the following setting values using [<,>(left/right)] button.
Value Description
RMC
Ignore the outdoor unit PCB’s low noise operation Switch Setting value
- Function setting – remote controller low noise operation time menu de-
activation
ODU(default)
It is controlled in the outdoor unit itself according to the outdoor unit
PCB’s low noise operation Switch Setting value
- Function setting – remote controller low noise operation time menu de-
activation
Human detection sensor
It is the function to set whether to install human detection sensor and operation standard value.
• In the installer setting list, after selecting human detection sensor setting category, if you press
[OK] button, it moves to the detail screen.
• You can set the following setting values for each category using [<,> (left/right)] button.
Value Description
Installation status Not installed, basic installation, 90º rotation installation
Detection result sending cycle 5 s, 30 s, 1 min., 3 min.
Sensitivity setting Standard, low sensitivity, high sensitivity