MultiSITE CRC 2 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Zigbee Ecosystem
Device Groups
Press the Device Groups button on the Zigbee Ecosystem screen to display the Device Groups monitoring screen. All values on this screen
are for monitoring purposes only and can not be changed.
Door status
Door installed
Win. status
Device Groups
Closed
Open
Yes
Water status
Yes
Yes
Normal
Win. installed
Water installed
Logical OR’d status for all installed Door sensors
Logical OR’d status for all installed Window sensors
Logical OR’d status for all installed Water Leak sensors
Alarms Configuration
Press the Alarms Configuration button on the Zigbee Ecosystem screen to configure a high and low temperature alarm for an installed Zigbee
temperature sensor. Alarming is reported at the bottom of the Home screen and represents a logical OR’d function for all currently paired
Zigbee temperature sensors. When the Ambient low temperature alarm threshold is exceeded, “Low temperature” will alarm on the Home
screen. When the Ambient high temperature threshold is exceeded, “High temperature” alarms on the Home screen.
Hysteresis
1/2 Temperature Alarms
On
2.0°F
Enable
Ambient low
1/2 Temperature Alarms
86.0°F
50.0°F
Ambient high
0.0 - 10.0 °F
(2.0 °F default)
32.0 - 122.0 °F
(86.0 °F default)
32.0 - 50.0 °F
(50.0 °F default)