Occ Auto Heat
74°
Indoor °F
Humidity
66 %
Auto
78
68
Automatic Heating / Cooling mode
In Automatic mode, the setpoint dis-
played at the top of the set point bar
located directly under the blue line
represents the occupied cooling setpoint
while the setpoint directly above the red
line represents the heating setpoint.
During occupied setpoints adjustment,
the large digits are temporarily used to
display the occupied “Cooling Setpoint”
or occupied “Heating Setpoint.” The
actual setpoint is dependent on the last
effective demand (heating or cooling).
The CRC setpoint adjustment defaults
to cooling adjustment first, regardless of
the current mode. To switch to heating
setpoint adjustment, tap either the up
or down arrow (“Cooling Setpoint” will
appear on the screen). Immediately tap
the Mode button to switch to heating set-
point adjustment. Each tap of the Mode
button will cycle through the available
adjustment types; cooling setpoint, heat-
ing setpoint and cool/heat setpoint. The
cool/heat setpoint adjustment simultane-
ously raises or lowers both setpoints.
Normal temperature display resumes
after the setpoints are adjusted and the
actual occupied heating and cooling set-
points are displayed in the setpoint bar.
CONTROLLER SETUP
Setpoint Adjustment continued