PREMTBVC Owners Manual
31
User Interface Guide
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Using the Up and Down arrows select
modes. The Test run will end after 18
mode can be interrupted by changing
IDU from the home screen.
Use this function to enable or
disable Group Control for the
system.
Using the Up and Down arrows select
a guard time of 0, 15, 30, 45 or 60
minutes.
Use this function to enable or
disable Indoor Unit Auto Start.
Master(1)
30 M in(2)
Cooling(1)
Test run(1)
Guard T imer(33)
IDU Au t o Start(39)
Enable(1)
IDU M ode- M/S(8)
Gr p Cntrl Funcs(19)
Di sable(0)
3/4 Installer / General
Parameter Parameter Settings Denition
Test run(1)
Default value = O
Initiates an IDU test mode
IDU Mode - M/S(8)
Default value = Slave(0)
Sets the IDU as a master or slave unit
Grp Cntrl Funcs(19)
Default value = Disable(0)
Enables additional common functions across IDUs when
Guard Timer(33)
30 min(2), 45 min(3), 60 min(4)
Default value = 15 min(1)
Protects the compressor against repetitive and short
duration changes in system mode
IDU Auto Start(39)
Default value = Enable(0)
Turns on the IDU automatically after power is restored to
the IDU
Installer