PREMTBVC Owners Manual

31
User Interface Guide
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Using the Up and Down arrows select
󰀨
modes. The Test run will end after 18
󰀨
mode can be interrupted by changing
󰀨
IDU from the home screen.
Use this function to enable or
disable Group Control for the
system.
Using the Up and Down arrows select
a guard time of 0, 15, 30, 45 or 60
minutes.
Use this function to enable or
disable Indoor Unit Auto Start.
Master(1)
30 M in(2)
Cooling(1)
Test run(1)
Guard T imer(33)
IDU Au t o Start(39)
Enable(1)
IDU M ode- M/S(8)
Gr p Cntrl Funcs(19)
Di sable(0)
3/4 Installer / General
Parameter Parameter Settings Denition
Test run(1) 󰀨
Default value = O󰀨
Initiates an IDU test mode
IDU Mode - M/S(8) 
Default value = Slave(0)
Sets the IDU as a master or slave unit
Grp Cntrl Funcs(19) 
Default value = Disable(0)
Enables additional common functions across IDUs when

Guard Timer(33) 
30 min(2), 45 min(3), 60 min(4)
Default value = 15 min(1)
Protects the compressor against repetitive and short
duration changes in system mode
IDU Auto Start(39) 
Default value = Enable(0)
Turns on the IDU automatically after power is restored to
the IDU
Installer