CONFIGURATION SCREENS
Temperature Settings
Press the Temperature Settings button on the Installer screen to display the Temperature Settings screen. Press the right
arrow button to display the second page of the Temperature Settings screen.
RC(1)
1/2 Temperatu re S ettings
Temp Se n s Loc(4)
0.5°C(1)
Set Point Prec. (17)
0°F
Temp Calib(61)
InternalTemp Sensor
4°F
Sing. SP Deadba n d
4°FDual SP Deadba n d
4°F/8°F (2)
2/2 Temperature Settings
Heat. Therm(15)
2°F/-2°F (3)
Cool. Therm(27)
Parameter Parameter Settings Denition
Temp Sens Loc (4) 1 = “RC” (1)”, 2 = “IDU (2)”, 3 = “2TH (3)”
Default value = RC(1)
Selects between sensing temperature at the remote
controller RC(1), the indoor unit IDU(2), or both
sensors 2TH(3)
Temp Calib (61)
0°F
Provides an adjustment for room temperature value
as reported by onboard sensor.
Setpoint °C Prec. (17) 1°C(0), 0.5°C(1)
Default value = 1°C(0)
Chooses whether to display Celsius temperatures
with 0.5 degree resolution or not
Single SP Deadband 1 = “2°F (1)” 5 = “10°F (5)”
2 = “4°F (2)” 6 = “12°F (6)”
3 = “6°F (3)” 7 = “14°F (7)”
4 = “8°F (4)”
Default value = Dual SP (when supported)
setpoint (the value chosen as your setpoint) and
cooling setpoint
Heat Therm(15) 0 = “Default (0)”
1 = “8°F/12°F (1)”
2 = “4°F/8°F (2)”
3 = “-2°F/2°F (3)”
4 = “-1°F/1°F (4)”
Default value = Default(0)
Provides an adjustable band around the heating
values
Cool Therm(27) 0 = “1°F/-1°F (0)”
1 = “12°F/8°F (1)”
2 = “8°F/4°F (2)”
3 = “2°F/-2°F (3)”
Default value = 1°F/-1°F (0)
Provides an adjustable band around the cooling
values
Minimum deadband value
between the heating and
cooling setpoints. Applied
only when any of the
Range is 1 °F - 10 °F
Installer