CONFIGURATION SCREENS
Accessories
Press the Accessories button on the Installer screen to display the Accessories screen.
Auto Off(0)
Disable(0)
1/3 Accessories
Dry Cont Enbl(41)
Dry cont. Auto(9)
CN_EXT Cnfg(52)
Out. Air-Vent(24)
StpIDUs(5)
Enable(1)
Plasma Kit(20)
Enable(1)
Grill Elev Kit(23)
Disable(0)
This option enables the related
control on the MORE screen that
turns the Vent kit on or off.
This option enables the related control
on the MORE screen that turns the
Plasma Purifier on or off.
This option enables the related
control on the Filter Functions
screen that controls Raise/Lower
Grill functions.
Installer
Parameter Parameter Settings Denition
Dry Cont Enbl(41) 
0 = “Default (0)”
1 = “Not Used (1)”
2 = “Enabled (2)”
3 = “Use CN_EXT (3)”
Default value = Default(0)
Enables use of a dry contact through the
CN_CC connector of the IDU
Dry cont. Auto(9) 󰀨
Default value = Disabled(0)
Enables auto run feature when used in
conjunction with a simple dry contact
CN_EXT Cnfg (52) 
0 = “Disable (0)”
󰀨
2 = “DryCntct (2)”
3 = “Stp1IDU (3)”
4 = Reserved
5 = “StpIDUs (5)”
Default value = Disabled(0)

(CN_EXT) will be used.

under White Papers and Controls for more
information on using the IDU onboard simple
dry contact.
Out. Air – Vent (24) 0 = “Disable (0)”, 1 = “Enable (1)”
Default value = Disabled(0)
Used to inform the IDU that a ventilation kit
is installed. Enabling this control enables a
related control on the More screen to control
ventilation.
Plasma Kit (20) 0 = “Disable (0)”, 1 = “Enable (1)”
Default value = Disabled(0)

function. A plasma kit is required.
Grill Elev. Kit (23) 0 = “Disable (0), 1 = “Enable (1)”
Default value = Disabled(0)
For cassette IDUs only when kit is installed.
Enables controls that allow lowering of the
