MultiSITE CRC 2 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Disable(0)
0.0% RH
Humidity calib.
ZB 1
CO2 source
2/3 Accessories
Refrig Leak Sns(29)
Disable(0)
Cntrlr Occ Sensor
30 min
Cntrlr Min Occ On
ZB 1
Humidity sensor
Global setting which applies to both
the onboard PIR sensor as well as any
installed Zigbee motion sensors.
CONFIGURATION SCREENS
Installer
Accessories – continued
Press the right arrow button on the 1/3 Accessories screen to display the 2/3 Accessories screen.
Parameter Parameter Settings Denition
Refrig Leak Sns(29)
Default value = Disabled(0)
Enables the refrigerant leak sensor
Cntrlr Occ Sensor 0 = “Disable”, 1 = “Enable”
Default value = Disabled(0)
Enables or disables the occupancy sensor,
either onboard PIR sensor or Zigbee
sensor(s)
Cntrlr Min Occ On
0 = “10 min (1)”
1 = “30 min (2)”
2 = “60 min (3)”
3 = “2 hrs (4)”
4 = “4 hrs (5)”
5 = “8 hrs (6)”
6 = “12 hrs (7)”
7 = “24 hrs (8)”
Default value = 10 min (1)
Time the controller will wait before the
occupancy status changes to unoccupied
when no motion is detected by the sensor
Humidity sensor
1-20 = “ZBx”, where x represents a paired
ZigBee humidity sensor
Default value = Internal
Enables or disables the occupancy sensor,
either onboard PIR sensor or Zigbee
sensor(s)
Humidity calib.
CO2 source
1-20 = “ZBx”, where x represents a paired
ZigBee CO2 sensor
None
Enables the use of room CO2 data when
CO2 sensor is installed